1-6. INSTALLATION DIAGRAM
MXZ-3A30NA
More than
100 mm
(3.94 in.)
Open as a rule
More than 500 mm (19.69 in.) if the back,
both sides and top are open
Units should be installed by licensed contractor according to local code requirements.
4
After the leak test, apply insulat-
ing material tightly so that there is
no gap.
When the piping is to be at-
tached to a wall containing metals
(tin plated) or metal netting, use
a chemically treated wooden
piece 20 mm (7.9 in.) or thicker
between the wall and the piping
or wrap 7 to 8 turns of insulation
vinyl tape around the piping.
Open as a rule
More than 500 mm
To use existing piping, perform
(19.69 in.) if the front
COOL operation for 30 minutes
and both sides are open
and pump down before removing
the old air conditioner. Remake
flare according to the dimension
for new refrigerant.
More than
100 mm (3.94 in.)
More than
200 mm (7.87 in.) if there are
obstacles to both sides
More than 350 mm (13.78 in.)
Outdoor unit installation
2-U-shape notched holes
(Base bolt M10)
Air in
Air out
2-12 (0.47) × 36 (1.42) Oval holes
(Base bolt M10)
PARTS TO BE PROVIDED AT YOUR SITE
(A) Power supply cord*
(B) Indoor/outdoor unit connecting wire*
(C) Extension pipe (Refer to 1-4.)
(D) Wall hole cover
(E) Piping tape
Extension drain hose
(F)
(or soft PVC hose, 15 mm (19/32 in.)
inner dia. or hard PVC pipe VP16)
(G) Refrigeration oil
(H) Putty
(I) Pipe fixing band
(J) Fixing screw for (I)
(K) Wall hole sleeve
Soft PVC hose, 25 mm (31/32 in.)
(L)
inner dia. or hard PVC pipe VP25
* Note:
Place indoor/outdoor unit connecting wire (B) and
power supply cord (A) at least 1 m (39.4 in.) away
from the TV antenna wire.
The "Q'ty" for (B) to (K) in the above table is quan-
tity to be used per indoor unit.
[Unit: mm (inch)]
1
1
1
1
1
1
Little
amount
1
2 to 7
2 to 7
1
1