Package contents (Fig� 3�1)
Product components (Fig� 3�2)
A Load module, power supply lead
B Designer trim
C Sensor module
Product dimensions (Fig� 3�3)
4� Electrical installation
The mounting location should be selected so that daylight is able to fall onto the light
sensor. An optional corner wall mount (product no. 648015 black or 035174 white) is
available for mounting the NightMatic 5000-3 COM1.
The supply lead consist of three wires:
L
= phase conductor (usually black, brown or grey)
N = neutral conductor (usually blue)
PE = protective-earth conductor (green/yellow)
= switched phase conductor (usually black, brown or grey)
Note on manual override function:
A power switch for switching ON and OFF can be installed in the mains supply lead.
This is a prerequisite for the manual override function (➔ "6� Funtion")
If the rubber seal is damaged, the cable entry openings must be sealed with an M16
or M20 (at least IP54) double seal cable gland.
For mounting on the wall, a condensation water drainage hole (Ø 5 mm drill bit) is
marked next to the rubber seal. This must be opened if necessary. (Fig� 5�2)
Connection examples (Fig� 4�1)
a Light without neutral conductor
b Light with neutral conductor
c Connection by means of two-circuit single-interruption switch for manual
and automatic operation
d Connection via two-way switch for manual override and automatic operation
Setting I:
Automatic operation
Setting II:
Manual operation, light permanently ON
18
Note: The system cannot be switched OFF, it is only possible to select operation
via setting I or II.
a) Load, lighting max. 2000 W (refer to Technical specifications)
b) Sensor connection terminals
c) Indoor switch
d) Indoor two-circuit single-interruption switch, manual, automatic
e) Indoor two-way switch, automatic, light permanently ON
Connecting several sensors in parallel (not illustrated)
In this case, it is important not to exceed a sensor's maximum connected rating.
In addition, all units must be connected to the same phase.
Note: The cable between two sensors must be no more than 50 m in length.
5� Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Choose an appropriate site to install the product. Make sure that no lamp is shining
light directly on the sensor.
Installation procedure (Fig� 5�1 + 5�2)
• Switch OFF power supply.
• Detach designer trim from sensor module.
• Disconnect sensor module from the load module.
• Connect to mains power supply. (Fig� 5�3)
• Insert fastening screw and mount load module.
• Fit sensor and load module together and screw into place.
• Switch ON power supply.
• Set functions. (➔ "6� Function / operation")
• Fit designer trim.
6� Function / operation
Factory settings
Twilight level:
1000 lux
Night economy mode:
OFF
Setting for morning hours: light ON in the morning
Remote controls RC5, RC8 or Smart Remote can be used for resetting to the factory
settings.
19