1. About this document

Please read carefully and keep in a safe place.
– Under copyright. Reproduction either in whole or in part only with our
consent.
– Subject to change in the interest of technical progress.
Symbols
!
Hazard warning!
Reference to other information in the document.
...

2. General safety precautions

• Disconnect the power supply before performing any work on the unit.
• During installation, the electric power cable to be connected must not be
live. Therefore, switch off the power first and use a voltage tester to make
sure the wiring is off-circuit.
• Installing the sensor involves work on the mains power supply. This work
must therefore be carried out professionally in accordance with national
wiring regulations and electrical operating conditions. (e.g. DE: VDE 0100,
AT: ÖVE / ÖNORM E8001-1, CH: SEV 1000)
• Only use genuine replacement parts.
• Repairs may only be made by specialist workshops.
3. IR Micro
Proper use
– Presence detector suitable for indoor ceiling mounting.
The sensor is connected to the control unit via a DALI bus.
The sensor uses the DALI line for communication and for supplying power.
Package contents (Fig. 1)
Product dimensions (Fig. 2)
- 14 -
Product components (Fig. 3)
A Fitting frame
B Plug connection
C Sensor enclosure with lens
D Designer trim
4. Installation / wiring
• Switch OFF power supply. (Fig. 4)
A clip-on ceiling adapter or a frame for fitting onto a mounting box is provided
(Fig. 5).
– Wiring diagram (Fig. 6)
Wiring up the sensor switch: under section 6 of VDE 0100520, a multi-core lead
containing both the mains voltage leads as well as the control leads (e.g. NYM
5 × 1.5 mm²) may be used for the wiring between sensor and DALI Application
Controller.
The lead between DALI Application Controller and sensor must be no longer
than 300 m (with 1.5 mm²). After installing and switching ON, the sensor flashes
for 10 seconds.
Connecting the mains power supply lead (Fig. 6)
Note on parallel connection:
Several sensors can be connected in a DALI-2 system. In this case,
the maximum number of DALI users must not be exceeded
(➜ "10. Technical specifications")
- 15 -