Lowara SM30 BSETF3 Instrucciones Para La Instalación Y El Uso página 41

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 140
6.2.2 PUMP START/STOP THRESHOLDS
Note: The THRESHOLDS parameters can be set only with a system with a pressure or level sensor.
The thresholds must be set considering the hydraulic performances of the pump (curve Q-H) and of the
type of system.
Phase
Display
0 THRESHOLDS
1
P1 STOP THRESH.
2
P1 START THRESH.
3
P2 STOP THRESH.
4
P2 START THRESH.
5
P3 STOP THRESH.
6
P3 START THRESH.
6.2.3 PUMPS STARTING ROTATION
Phase
Display
0 PUMPS ROTATION
1
PUMPS ROTATION
2
PUMP SEQUENCE
3
SWITCH INTERVAL
NOTE: The jockey pump, if present, is not subject to rotation and is started first, it remains on when the
duty pumps start and it switches off last.
Comment
Application with pressure / level
Stop (OFF) threshold (pressure/level) for
pump 1
Start (ON) threshold (pressure/level) for
pump 1
Stop (OFF) threshold (pressure/level) for
pump 2
Start (ON) threshold (pressure/level) for
pump 2
Stop (OFF) threshold (pressure/level) for
pump 3
Start (ON) threshold (pressure/level) for
pump 3
Comment
Enable pump rotation.
Set YES to activate pump rotation. Automatic
pump rotation takes place each time the set is
restarted after stopping in automatic mode.
The jockey pump, if present, is not subject to
rotation, so it always starts first.
Insert the duty pump that you want to start
first after electrically switching on the set.
In systems with a jockey, as this is P1, the first
duty pump that can be set can only by P2 or
P3.
If automatic pump rotation does not take place
(the set has never been able to stop), after the
set time a "forced" rotation of the duty pumps
is performed (excluding the jockey).
To disable this function set 0h
Field
Default
0.. FS
+3.50 bar
0.. FS
+2.70 bar
0.. FS
+3.40 bar
0.. FS
+2.60 bar
0.. FS
+3.30 bar
0.. FS
+2.50 bar
Field
Default
YES
NO
P1
P2
P3
0 h
1÷12 h
en
YES
P1
0 h
41

Publicidad

Tabla de contenido
loading

Tabla de contenido