Connection and assembly

The FB filter must be installed on a ventilation line,
upstream from the fan/heat recovery sistem,
upstream from the noise attenuator NA, and if
present, upstream from the air heater AH. To install
the air filter, it is sufficient to insert it into the tube (Fig.
1).
1 1
The appliance is connected to the system by means
of a forced insertion on two cylindrical fittings in
galvanised steel with circular rubber built-in "T" seals.
Leave sufficient space to allow the filter to be cleaned
or replaced.

Technical data

Filtering class:
F7
Filtering media:
F7 Filter: composit polypropylene
Max operating temperature:
F7: 70° C
Dimensions: fig 2.
2 2
E
C
D
Mod.
A
B
235
285
FB 500
405
315
FB 800
FB 1200
470
370
560
485
FB 2000
630
515
FB 2500
710
608,5
FB 4000
FB 6000
710
805
VORT NRG
FB
A
C
D
E
300
200
400
300
250
400
600
315
700
600
315
700
700
355
800
900
450
1000
900
450
1000
NA
Curves of the initial load loss of filters:
Diagrams pag. 18.

Maintenance/cleaning

Check the filter from time to time and, if necessary,
replace it. Non reconditionable filters, which have to
be replaced when the loss of pressure is 1.5 times
above the loss that occurs when the filter is cleaned.
Clean the filter with mechanical means, a vacuum
cleaner or compressed air.