ZENITH-P
2.1 TYPE OF PROTECTIONS
ATEX / IECEx :
Ex eb IIC Gb
Ex tb IIIC Db
2.2 EXAMPLE OF MARKING LABEL
Figure 2 – Example of marking Label
2.3 CERTIFICATES
Atex Components Certificate - IMQ 19 ATEX 033 U
IECEx Components Certificate - IECEx IMQ 19.0004 U
2.4 ENCLOSURE'S DEGREE OF PROTECTION
IP 66
2.5 SERVICE TEMPERATURE
The equipment is certified for service temperature in the range Ta –60°C +100°C and should not be used outside these ranges.
The user must submit the complete unit for EU-Type examination by a Notified Body if it is to be used in a
hazardous area. The Installation, Operation and Maintenance Instructions must be always included with the
certified electrical apparatus.
3. INSTALLATION
Installation shall be carried out by suitably trained personnel in accordance with the applicable code of
practice (e.g. IEC / EN 60079-14) and the provisions of the national safety and accident prevention regulations
and this instruction manual.
3.1 SAFETY INSTRUCTIONS
The IP rating of the enclosure shall be maintained for the area of installation by the use of correct arrangement of cable-gland,
blanking plug elements & sealing and in accordance with the installation rules. Where other certified components are part of the
assembly, the user must take account of any limitation listed on relevant certificates.
Where enclosures are to be drilled use equipment that is suitable for the material of the enclosure (GRP polyester) and ensure that
the correct drilling speeds / feed rates are used. The holes must be cut inside the approved drilling areas for each wall, and must
be done with absolute quality and without burrs.
Due to the 4 mm thickness enclosure, is possible to thread the holes.
These instructions assume that the required cable entries have been pre-drilled (and may be threaded) on the enclosure. The cable
glands are usually fitted during installation.
The enclosure must be installed in absence of damage and free of defects.
MP39688
14
ZP91041-2