Interlogix TDA74 Serie Manual Del Usuario página 13

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 28
2.
Configure Ethernet details: 3, Enter.
If configuring for fixed IP:
Enter IP mode: 1, Enter.
Set Static: 2, Enter.
Enter IP address: 2, Enter. Set module IP address using
Menu as full stop.
Enter Subnet mask: 3, Enter. Set subnet mask using
Menu as full stop.
Enter Gateway: 4, Enter. Set gateway address using
Menu as full stop.
If configuring for DHCP:
Enter IP mode: 1, Enter.
Set DHCP: 1, Enter.
3.
Configure GPRS details:
Configure APN: 1, Enter. Press an appropriate key
repeatedly to select the correct character. The cursor
moves on after a few seconds, or when another key is
pressed. Use Menu to go back a space and Enter to
confirm.
Configure Username: 2, Enter. Press an appropriate key
repeatedly to select the correct character. The cursor
moves on after a few seconds, or when another key is
pressed. Use Menu to go back a space and Enter to
confirm.
Configure Password: 3, Enter. Press an appropriate key
repeatedly to select the correct character. The cursor
moves on after a few seconds, or when another key is
pressed. Use Menu to go back a space and Enter to
confirm.
4.
Configure OH settings: 6, Enter.
Configure OH protocol version: 1, Enter. Select desired
protocol version: 1 = V1.9.3, 2 = V2.
Configure Receiver number: 2, Enter. Press Menu to back
a space, Enter to accept.
Configure Line number: 3, Enter. Press Menu to back a
space, Enter to accept.
Configure Ethernet path heartbeat interval: 4, Enter. Enter
an interval value between 0 and 255.
Configure Ethernet path interval unit: 5, Enter. Enter the
desired Ethernet interval units: 1 = seconds, 2 = minutes,
3 = hours.
Configure GPRS path heartbeat interval: 6, Enter. Enter
an interval value between 0 and 255.
Configure GPRS path interval unit: 7, Enter. Enter the
desired Ethernet interval units: 1 = seconds, 2 = minutes,
3 = hours.
Configure Alarm protocol: 8, Enter. Enter the desired
alarm format: 1 = (X)SIA, 2 = CID.
Primary Ethernet receiver IP address: 9, Enter. Set IP
address using Menu as full stop.
Primary GPRS receiver IP address: 10, Enter. Set IP
address using Menu as full stop.
Backup Ethernet receiver IP address: 11, Enter. Set IP
address using Menu as full stop.
P/N 1079518 (ML) • REV D • ISS 15OCT13
Backup GPRS receiver IP address: 12, Enter. Set IP
address using Menu as full stop.
Primary Ethernet port number: 13, Enter. Set port number.
Use Menu to back a space and Enter to accept.
Primary GPRS port number: 14, Enter. Set port number.
Use Menu to back a space and Enter to accept.
Backup Ethernet port number: 15, Enter. Set port number.
Use Menu to back a space and Enter to accept.
Backup GPRS port number: 16, Enter. Set port number.
Use Menu to back a space and Enter to accept.
Transmitting to a VdS receiver
Using the built-in menu:
1.
Set Reporting mode: 2, Enter.
Set VdS: 3, Enter.
2.
Configure Ethernet details: 3, Enter.
If configuring for fixed IP:
Enter IP mode: 1, Enter.
Set Static: 2, Enter.
Enter IP address: 2, Enter. Set module IP address using
Menu as full stop.
Enter Subnet mask: 3, Enter. Set subnet mask using
Menu as full stop.
Enter Gateway: 4, Enter. Set gateway address using
Menu as full stop.
If configuring for DHCP:
Enter IP mode: 1, Enter.
Set DHCP: 1, Enter.
3.
Configure VdS details: 7, Enter.
Primary receiver IP address: 1, Enter. Set desired primary
receiver IP address using Menu as full stop.
Primary receiver port number: 2, Enter. Set desired
primary receiver port number. Use Menu to back a space
and Enter to accept.
Primary receiver connection type: 3, Enter. Enter desired
receiver A connection type: 1 = Eth/GPRS, 2 = Eth only, 3
= GPRS only.
Primary receiver key number: 4, Enter. Set desired
primary receiver key number. Use Menu to back a space
and Enter to accept.
Primary receiver encryption key: 5, Enter. Set desired
primary receiver encryption key. Use Menu to back a
space, and Enter to accept. Use digit keys to enter
hexadecimal digits from ranges 0 to 9 and A to F.
Primary alternative path test time: 6, Enter. Set desired
primary alternative path test time. Use Menu to back a
space and Enter to accept.
Backup receiver IP address: 7, Enter. Same as for primary
receiver IP address.
Backup receiver port number: 8, Enter. Same as for
Primary receiver port number.
Backup receiver connection type: 9, Enter. Same as for
Primary receiver connection type.
13 / 84

Publicidad

Tabla de contenido
loading

Tabla de contenido