Hazards / Risks
1.
Electric shock. The model is equipped with fan motors and,
as an optional, electric defrost heaters. It is important to use
electrical safety systems that are in compliance to the
regulations in force.
2.
Burns. The surface of the electric defrost heaters can reach
the temperature of 350 ° C.
3.
Cuts. The heat exchanger is made with fins with sharp edges
and the casing is made of sheet metal parts.
4.
Parts in motion. The model is equipped with fan motors fitted
with external protection.
5.
Crushing. The weight of unit may exceed 25 kg.
Reference standards and directives
-
MACHINES DIRECTIVE 2006/42/EC
-
LOW-VOLTAGE DIRECTIVE 2014/35/UE
-
ELECTROMAGNETIC COMPATIBILITY DIR. 2014/30/UE
-
PED DIRECTIVE 2014/68/UE
-
ERP DIRECTIVE 2009/125/EC
-
REFRIGERATING SYSTEMS AND HEAT PUMPS UNI EN 378
Manufacturing and dimensional features
MIC model
Dimensions
A
(mm)
B
C
D
Coil inner connections
In (SAE)
Out (mm)
Drain connection
GAS
Net weight
kg
(*) Use thermal expansion valve with external pressure equalizer.
Instructions for a correct installation
Recommended distances
For the installation of more than one unit in the same cold or air-
conditioned room it is necessary to observe the dimensions in-
dicated in drawing.
Inner drip tray
Heaters
80 - 81
101 (*)
161 (*)
430
430
730
320
320
620
172
172
185
30
30
30
1/2
1/2
1/2
12
16
16
1/2"
1/2"
1/2"
7,3
8,0
12,2
Fastening detail "F"
Positioning detail of electric heaters
Heater clips
201 (*)
301 (*)
401 (*)
730
1030
1330
620
920
1220
185
185
185
30
30
35
1/2
1/2
1/2
16
22
22
1/2"
1/2"
1"
13,4
19
24,4
www.modinecoolers.com
501 (*)
1630
1520
185
35
1/2
22
1"
29,9
11