6
Listed accessories for use with Wöhner busbar support only
All devices are suitable for use in branch and feeder circuits
Art. 01437
CR185-B*
Art. 01442
CR185-A80*
only for use on a system
carrying maximum 1400A
SCCR
Busbar
[kA]
[mm]
42
30x10 - 40x10
50
60x10 - 120x10
1000Vac/Vdc/1400A/3ph
Wire
Torque Values
Size
[Nm]
Bus Bar Cable
Busbar 2x
80 x 10 mm
20 - 24
Technische Änderungen vorbehalten.
Wöhner GmbH Co.
KG
, Mönchrödener Str. 10, 96472 Rödental, Germany
www.woehner.com
*Type No. according to
Art. 01443
CR185-A2x12*
only for use on a system
carrying maximum 1520A
SCCR
Busbar
[kA]
[mm]
42
30x10 - 40x10
50
60x10 - 120x10
1000Vac/Vdc/1520A/3ph
Wire
Torque Values
Size
[Nm]
Bus Bar Cable
4x
500 kcmil
20 - 24
Subject to change without notice.
Art. 01441
CR185-A2x300*
SCCR
[kA]
35
1000Vac/Vdc/840A/3ph
Wire Size
4x350 kcmil
up to
600 kcmil
30
Busbar
[mm]
30x10 - 120x10
Torque Values
[Nm]
Bus Bar
Cable
25 - 30
20 - 24
94709000A Index c