PRELIMINARY
FUNCTION
DESCRIPTION
Advanced Functions
Selects the allowed input
frequency range for the
Input frequency
switch to bypass and
tolerance
synchronization of the
output
Selects the voltage range
Bypass voltage
Low:
allowed for the switch to
thresholds
High:
bypass
Selects the allowed
Bypass voltage
Low:
voltage range for
thresholds for ECO
High:
operation in ECO mode
Selects the activation
Activation sensitivity
sensitivity for operation in
for ECO
ECO mode
Power supply of load on
Power supply of load
bypass with UPS off
in stand-by
NOT powered)
(stand-by status)
Selects operating mode of
Bypass operation
bypass line
High sensitivity
Inverter
Selects the source of
synchronization
synchronization for the
From bypass line
(External Sync)
inverter output
Selects the pause time for
automatic reactivation
Power-on delay
after mains power has
been restored
Enables the mode for
Power Walk-in
gradual return to mains
power
Sets the duration of the
Duration of
gradual return to mains
Power Walk-in
power (only if Power
Walk-in is enabled)
Speed of
Selects the speed of
synchronization
synchronization between
between inverter and
the inverter and the
bypass line
bypass line
Enables reading of the
External temperature
external temperature
probe (optional)
probe
* When these output voltage values are set, the output power of the UPS is reduced (see "Reducing the Load (to 200V and
208V)" paragraph)
All manuals and user guides at all-guides.com
DEFAULT
POSSIBLE SETTINGS
• ± 0.25%
• ± 0.5%
± 5%
• ± 0.75%
• ± 1 ÷ ±10 in steps of 1%
180V
Low: 180 ÷ 200 in steps of 1V
264V
High:
250 ÷ 264 in steps of 1V
200V
Low: 180 ÷ 220 in steps of 1V
253V
High:
240 ÷ 264 in steps of 1V
• Low
• Normal
Normal
• High
• Disabled (not powered)
Disabled (load
• Enabled (powered)
• Enabled / High sensitivity
• Enabled / Low sensitivity
• Disabled with input / output
Enabled /
synchronization
• Disabled without input / output
synchronization
• From bypass line
• From external input
• Disabled
5 sec.
• 1 ÷ 255 in steps of 1 sec.
• Enabled
Disabled
• Disabled
10 sec
Min.: 1 sec. - Max.: 30 sec.
• 0.5 Hz/sec
• 1 Hz/sec
1 Hz/sec
• 1.5 Hz/sec
• 2 Hz/sec
• Not enabled
Not enabled
• Enabled
87
MOD.
C
OMMUNICATION
The rear panel of the UPS (see Rear View of the UPS) contains the following communication ports:
Ø
SW
Serial port available with RS232 connector and USB connector.
NOTE: the use of one connector automatically excludes the other.
Ø
Expansion slots for additional COMMUNICATION SLOT interface boards
On the front, covered by the terminal-cover, there is another expansion slot for the power relay board (optional 250Vac, 3A, 4
programmable contacts)
SW
RS232
USB C
AND
SW
CP
SW
SW
PIN #
NAME
1
2
TX
3
RX
SW
4
5
GND
POWER
6
CP
7
8
+15V
POWER
SW
9
WKATX
C
S
SW
OMMUNICATION
The UPS is equipped with two expansion slots for accessory
communication boards that enable the equipment to communicate
using the main communication standards.
Some examples:
SW
Ø
Second RS232 port
Ø
Serial duplicator
Ø
Ethernet agent with TCP/IP, HTTP and SNMP protocol
SW
Ø
RS232 + RS485 port with JBUS / MODBUS protocol
For further information on the accessories available, visit the web site.
PRELIMINARY
P
ORTS
ONNECTORS
RS232 CONNECTOR
TYPE
SIGNAL
IN
OUT
Serial line TX
IN
Serial line RX
OUT
Isolated power supply
15V±5% 80mA max
OUT
ATX power supply wake-up
LOTS
88
USB CONNECTOR
4
3
1
2
PIN #
SIGNAL
1
VBUS
2
D-
3
D+
4
GND