LEGRAND Wattstopper LMCP8-10V Instrucciones De Instalación página 4

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Step 1 Mount the LMCP Enclosure
1. Attach the enclosure to the wall. The enclosure should be level,
plumb and rigidly installed. Refer to the instructions provided with
the enclosure for flush or surface mounting procedures.
2. Determine the appropriate wire entry locations. Make sure that
all line and low voltage wiring entry locations are confined to the
appropriate compartments as shown in the diagram below.
All wires routed into the low voltage section must originate and remain Class 2, or they must be reclassified.
3. Drill or knock out openings to bring wiring conduit into the enclosure.
13.58"
15.08"
26"
16.34"
Step 2 Install the LMCP Interior
Do not install the interior assembly until after the LMCP enclosure has been securely mounted to the wall and the conduit/wiring holes
have been drilled or knocked out.
NOTE: If this enclosure includes the optional DMP-1 Din Rail Mounting Plate (to allow for installation of EM-IN Emergency Interior
contactors), place DMP Plate over lower studs before installing the interior.
1. Place the interior in the enclosure and align the interior with the studs provided in the enclosure.
2. Attach the interior assembly to the back of the enclosure using the four sets of nuts and washers provided.
3. After all wiring is completed, attach the cover according to the instructions provided with the enclosure.
Step 3 Connect the AC Power Supply to Power Source
VERIFY WHETHER THE SUPPLY LINE VOLTAGE IS 115VAC, 240VAC, 277VAC, OR 347VAC AND THAT THE POWER
SUPPLY IN THIS PANEL MATCHES THAT LINE VOLTAGE. WIRING TO THE INCORRECT VOLTAGE TERMINAL MAY
RESULT IN DAMAGE TO THE POWER SUPPLY AND/OR THE PANEL, AND WILL VOID THE PRODUCT WARRANTY.
The LMCP has several power supply options that allow it to operate with 115VAC, 240VAC single phase, 277VAC or 347VAC line
voltage. These power supplies function with either 50 or 60 Hz. They have internal overcurrent protection. The transformer automatically
turns OFF when overloaded and resets when the fault is removed. The power supply contains MOVs to protect all downstream
electronics from transient power line voltage surges.
1. Read and remove the CAUTION label covering the terminals.
2. Note that there are different terminals for supply voltage input. Wire to ONLY ONE of these terminals. Match the input voltage to
the correct terminal.
LENC8S
LENC8F
4.82"
11.68"
15.08"
Low
voltage
(15.75" w/ cover)
section
23.34"
14.5"
16.5" (16.62" w/cover)
8.08"
LENC8-24S
12.2"
11.68"
Low
voltage
section
23.34"
31.42"
(32" w/cover)
16"
20.54"
23.88" (24" w/ cover)
INSTALLATION
WHEN ROUTING CONDUIT AND WIRE
LENC24S
LENC24F
4.94"
4.94"
14"
Low voltage
section
26"
31.42"
(32" w/cover)
16"
23.88" (24" w/ cover)
LENC24-48S
4.94"
4.94"
14"
Low voltage
section
43.88"
(44.5" w/cover)
40.5"
16"
23.88" (24" w/ cover)
Enclosure dimensions
WARNING
4
CAUTION
OBSERVE LINE AND LOW
VOLTAGE SEPARATION
LENC48S
LENC48F
4.94"
4.94"
14"
43.88"
(44.5" w/cover)
Low voltage
35.8"
section
40.5"
8.08"
16"
23.88" (24" w/ cover)
Panel enclosures come as surface mount ("S") or
flush mount ("F").
For flush mount enclosures, add 1.35" to height and
1.85" to width.
Depth for all models 4.5", with cover attached 4.67"

Publicidad

Tabla de contenido
loading

Tabla de contenido