3 Technical description
12
and cables to the transformer, however, account must be taken of
the higher output and lower output voltage of the Conergy IPG
300K.
Specifications of the transformer required when using a
Conergy IPG 300K:
Medium voltage side
In accordance with the specifications of the energy supply
company (ESC)
Low voltage side
Interlinked voltage
Nominal capacity
Vector group
Short circuit voltage
Level of performance
Differentiation is made between seven levels of performance for
Conergy IPG series central inverters, depending on system
dimensioning. This results in the following type descriptions:
Model description
Conergy IPG 40K
Conergy IPG 60K
Conergy IPG 80K
Conergy IPG 100K
Conergy IPG 110K
Conergy IPG 280K
Conergy IPG 300K
Conergy IPG series central inverters are delivered in three different
sizes of housing according to their level of performance.
Conergy IPG 40K–60K
Height
Width
Depth
Weight Conergy IPG 40K
Weight Conergy IPG 60K
Conergy IPG 80K–110K
Height
Width
Depth
Weight
Operating manual
270 V
(3 phases, N, PE)
eff
270 kVA
Dyn5
<= 6 %
Output power
36 kW
54 kW
72 kW
90 kW
100 kW
250 kW
270 kW
1800 mm
610 mm
800 mm
540 kg
610 kg
1800 mm
1210 mm
800 mm
1220 kg
Conergy IPG series central inverters