Maintenance; Maintenance Interval; Safety Instructions; Carrying Out Maintenance - Conergy IPG Serie Instrucciones De Servicio

Ocultar thumbs Ver también para IPG Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

6

Maintenance

6.1
6.2
6.3
Conergy IPG series central inverters

Maintenance interval

The maintenance work described below must be carried out every
two years after the date of installation.
This period may be shortened owing to local conditions. Reasons
for a shortened maintenance interval are:
| High level of stress caused by deposits of dirt or dust e.g. in
agricultural firms
| Vibration e.g. caused by setting the device up in locations in
direct proximity to railway lines or arterial roads
| High number of nominal load hours e.g. in tracked systems
| Constantly high or sharply fluctuating ambient temperatures e.g.
desert or steppe locations.

Safety instructions

During all maintenance work
| disconnect all electrical systems and live parts and secure them
against switching back on;
| ensure that a second person is present, who can provide
immediate assistance in the case of an electrical accident;
| before starting work on the device, check that all relevant parts
are deenergised;
| cover nearby live parts;
| observe safety equipment, warning and safety instructions on the
unit and in this operating manual.

Carrying out maintenance

Preparations for maintenance work
1. Open the front doors.
2. Switch off the auxiliary power supply.
3. For Conergy IPG 80K–300K, unscrew the lower Plexiglas cover.
4. For Conergy IPG 80K–300K, remove the Plexiglas cover.
Operating manual
6 Maintenance
45

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ipg 40kIpg 60kIpg 80kIpg 100kIpg 110kIpg 280k ... Mostrar todo

Tabla de contenido