9. Specifications

9. Specifications
Specifications
EN
Measuring range
Measuring range
Overload safety
Increased overload safety
(option)
Vacuum-tight
Digital display
Model
Output signal
Output signal
Load
IO-Link (option)
Revision
Rate
Min. cycle time
Master port class
Zero point setting
Damping of analogue output/
switching outputs
28
see product label
The overload safety is based on the sensor element used. Depending on the selected process
connection and sealing, restrictions in overload safety can result.
Measuring ranges ≤ 600 bar [< 8,000 psi]: 2-fold
Measuring ranges to 1.000 bar [≥ 8,000 psi]: 1.5-fold
Deviating temperature errors and long-term stability with respect to the selected measuring
range apply here.
Yes
7-segment LED, 2-coloured red/green, 4-digit, 8.9 [0.35 in] character size
Display can be turned electronically by 180°
Colour ranges through green/red switching can be parameterised
Display can be rotated mechanically through 335°
see product label
4 ... 20 mA
DC 0 ... 10 V
1.1
38.4 kBaud (COM2)
2.3 ms
A
max. 3 % of span
configurable from 0 ms ... 65 s
≤ 500 Ω
> max. output voltage / 1 mA
WIKA operating instructions, model PSD-4-ECO