Battery Replacement; Storage And Service - Tripp-Lite AG-02F0 Serie Manual Del Propietário

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Battery Replacement

Under normal conditions, the original battery in your UPS will last several years. Battery
replacement should only be performed by qualified personnel. Refer to "Battery Warnings" in
the Important Safety Instructions section for more information.
Models OMNIVS800LCD, OMNIVS1000LCD, OMNIVS1200LCD and OMNISMART700TSU
require two 12V DC, 7Ah replacement batteries
Model OMNIVS1500LCD requires two 12V DC, 9Ah replacement batteries.
For further information about replacement compatibility and ordering, visit
www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and
quantity: 12V DC sealed lead-acid, 6-cell and in compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches and rings. High energy
passing through conductive materials may cause severe burns.

Storage and Service

Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from
the UPS. Press the power button and disconnect the unit from AC power. Your UPS will be
completely turned off (deactivated), and will be ready for storage. If you plan on storing your
UPS for an extended period, fully recharge the UPS batteries every three months. Plug the
UPS into a live AC outlet and allow the batteries to recharge for 4 to 6 hours. If you leave
your UPS batteries discharged for a long period of time, they will suffer a permanent loss of
capacity.
18-10-316-9338D9.indb 10
10
12/27/2018 1:30:23 PM

Publicidad

Tabla de contenido
loading

Tabla de contenido