Operation; Phase Rotation Direction - AEMC Instruments 6608 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.1 Phase Rotation Direction

On a three-phase electrical network:
1.
Connect the three leads to the instrument, matching the mark-
ings.
2.
Connect the three alligator clips to the 3 phases of the network
to be tested.
3.
The display lights up, indicating that the instrument is in opera-
tion.
4.
When the three phase indicators (L1, L2, L3) are lit, the
clockwise (or counter-clockwise) rotation arrow indicates the
direction of phase rotation.
Warning: The wrong direction of rotation may be displayed if a lead
is connected in error to the neutral conductor.
Refer to the instrument's back label for a summary of the various
display possibilities.
Phase Rotation Meter Model 6608
CHAPTER 4

OPERATION

7

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido