Installation Guide

OpEraTiON

The HZ322 TrueZONE panel contains an LED display that communicates system and
zone status. The LEDs indicate the following information.
Much of this information, as well as configuration information, is listed on the label
on the inside of the HZ322 cover. For users who prefer French or Spanish labels,
they are provided on page 16. Cut them out and attach them to the inside of the
HZ322 cover.
LED
Description
HEAT 1
Solid when in heat stage 1. Blinking when DATS high limit mode has
been reached.
HEAT 2
Solid when in heat stage 2. Blinking when stage 2 locked out due to
DATS or OT.
COOL 1
Solid when in cool stage 1. Blinking when DATS low limit mode has
been reached.
COOL 2
Solid when in cool stage 2. Blinking when stage 2 locked out due to
DATS.
PURGE
Solid when in purge (at power-up and after a call for heat or cool).
Blinking when the DATS sensor has failed, or the wires are shorted or
open. Will blink for 3 minutes at power-up if DATS is not present.
FAN
Solid with a call for fan.
EM HEAT
Solid when in emergency heat mode. This light does not indicate a call
for heat. Emergency heat will only run when both HEAT and EM HEAT
are lit.
ZONE 1, 2, 3 Solid green when open or opening. Solid red when closed or closing.
Blinking amber when there is a damper or thermostat short circuit (cir-
cuit breaker trip).

CHECkOuT

To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the
Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on
page 6 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation.
Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or
cool and viewing the active wires as displayed on the LCD screen.
Checkout Step
1.
Display shows OT
2.
Display shows DATS
3.
Heat stages test
4.
EM Heat stages test
5.
Cool stages test
6.
Fan Test
7.
Damper 1 test
8.
Damper 2 test
9.
Damper 3 test
10. View Tstat1 inputs
11. View Tstat2 inputs
12. View Tstat3 inputs
13. Exit checkout mode?
14. Exiting checkout mode
69-207EFS—0
Table 6. LED Operation.
Table 7. Checkout.
Line 1 display
Line 2 Display
OT SENSOR VAL
current OT temp (dynamic)
DAT SENSOR VAL
current DATS (dynamic)
TEST HEAT
[OFF] 1 2
TEST EMERG HEAT [OFF] 1 2
TEST COOL
[OFF] 1 2
TEST FAN
[OFF] ON
TEST Z1 DAMPER
[OPEN] CLOSED
TEST Z2 DAMPER
[OPEN] CLOSED
TEST Z3 DAMPER
[OPEN] CLOSED
ZONE1 STAT INPTS Displays active Tstat1 terminals
ZONE2 STAT INPTS Displays active Tstat2 terminals
ZONE3 STAT INPTS Displays active Tstat3 terminals
EXIT CHECKOUT?
(NEXT = EXIT)
EXITING
CHECKOUT
Notes:
All zone dampers open, all other relays OFF.
Heat turns on (fan also turns on if configured for fan on in heat).
Emergency heat turns on (fan also turns on).
Cooling turns on (fan also turns on).
Fan cycles on and off.
Cycles damper position with fan on.
Cycles damper position with fan on.
Cycles damper position with fan on.
Tests thermostat wiring with HVAC off.
Tests thermostat wiring with HVAC off.
Tests thermostat wiring with HVAC off.

HZ322
HEAT 1
HEAT 2
ZONE 1
COOL 1
COOL 2
ZONE 2
FAN
PURGE
ZONE 3
EM HEAT
EMERGENCY
HEAT
M28026
Fig. 14