9. Control Panel
Output Voltage
Bypass Voltage Range
Bypass Frequency Range
Converter Mode
ECO Mode
Bypass Mode
Auto Restart
Cold Start
Battery Mode Delay Time
System Shutdown Time
System Restore Time
Redundancy
Charger Test
9.3.6.3 Battery
The SETUP – BATTERY screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.5 for details.
BATTERY CAPACITY IN Ah
MAXIMUM CHARGING
BATTERY
SmartOnline SV-Series UPS Operating Mode
Standby
Bypass
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
CURRENT
BATTERY LOW /
SHUTDOWN SETTING
BATTERY TEST
BATTERY AGE ALERT
TEMPERATURE
COMPENSATION
Line
Battery
Battery Test
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Table 9.4
Battery Capacity in Ah
Maximum Charging Current
Battery Low Voltage
Battery Low Capacity
Battery Shutdown Voltage
Periodic Battery Test
Battery Test Interval
Stop by Time
Stop by Battery Voltage
Stop by Battery Capacity
Battery Age Alert
Temperature
Compensation
26
Fault
Converter
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Set battery capacity (0-999) (Default: 009)
Set maximum battery charging current (1-64A)
(Default: 2 for UPS system)
Set battery low voltage: (10.5-11.5V) x (number of
batteries) (Default: 110V)
Set battery low capacity (20-50%) (Default: 20%)
Set voltage point for system shutdown
(10-11V) x (number of batteries) (Default: 100)
Set 'Disable' or 'Enable' (Default: Disabled)
Set battery test interval (7-99 days) (Default: 30)
Set testing time for battery test (10-1000 sec)
(Default: 10)
Set battery voltage cut-off to end battery test
(11-12V) x (number of batteries) (Default: 110V)
Set battery capacity cut-off for battery test (20-50%)
(Default: 20)
Set battery age for replacement alert
(Disable, 12-60 months) (Default: Disable)
Set battery compensation (-5 ~ 0)
(Default: 0)