From Controller
+
Beacon
-
+
Sounder
1st Stage
-
2nd Stage
3rd Stage
Installation Manual
EN
Installation
a. The sounder is installed by first mounting the base unit and making the
external wring connections to the base. The head unit then automatically
connects when it is attached to the base.
b. The sounder head is separated from the base by unlocking the four
¼-turn fasteners in the corners of the sounder.
(Recommended screwdriver: Philips No. 2, min 100mm long).
c. Note that the head only fits onto the base one way around. If a beacon
is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached
Wiring
The sounder and beacon have separate wiring terminals. Each terminal is
duplicated to enable simple 'daisy-chain' connection of multiple units.
Line
Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)
Controls
a. Tone Selection
The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.
b. Volume Control
The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.
c. Beacon Flash Controls (If fitted)
The flash mode of the beacon can be altered using the 2-way
dipswitch marked
www.acornfiresecurity.com

Installation Instructions

1st Unit
Terminal Marking
+
-
S2
S3
+
-
www.acornfiresecurity.com
Nexus 120 DC Sounder & Sounder-Beacon
XENON BEACON
Switch
Off
1
60 flashes per min 30 flashes per min Single Flash Double Flash
2
Single Flash

Technical Specification:

Supply Voltage Range ................10-60V DC
Current – Sounder ...................... 0.12-0.55A* (Typ. 0.5A @ 24V, Tone 2)
Current – Xenon Beacon ............ 350mA peak @ 24V DC
(Where Fitted)
Current – LED Beacon ................ 18mA (Flashing)*
(Where Fitted) ............................. 65mA (Static)*
Peak Sound Level .......................110-120 dBA at 1m*
Number of Tones ........................ 64
Volume Control ........................... 20dBA typical
Remote Tone Switching ..............Provision for 3 alarm stages
Operating Temperature ............... - 25°C to +70°C
Casing......................................... High Impact Polycarbonate/ABS
IP Rating ..................................... IP66
Synchronisation .......................... Automatic with Klaxon Nexus and
*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.
The European directive "Waste Electrical and Electronic Equipment"
(WEEE) aims to minimise the impact of electrical and electronic
equipment waste on the environment and human health. To conform
with this directive, electrical equipment marked with this symbol
must not be disposed of in European public disposal systems.
European users of electrical equipment must now return end-of-life
equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.
To Next Unit
2nd Unit
LED BEACON
On
Off
Double Flash
Flashing
(60 single flashes per min.)
700mA peak @ 12V DC
(60 single flashes per min.)
(Typ. 120dBA @ 24V, Tone 2)
(Negative voltage activation)
Sonos Sounders
On
Static

Publicidad

Tabla de contenido
loading

Tabla de contenido