Brazing Of Piping; Piping Length And Refrigerant Charge; Additional Refrigerant Charge For Standard Diamenter Piping Based On Length; Hydraulic Connection Of The Condensate Drain - Mitsubishi Electric MULTIDENSITY 009 Manual De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 73
MULTIDENSITY
M-->F adapters
3/4' --> 5/8'
COPPER RED. MF 3/4' --> 5/8'
5/8' --> 1/2'
COPPER RED. MF 5/8' --> 1/2'
5/8' --> 3/4'
COPPER RED. MF 5/8' --> 3/4'
7/8' --> 1/2'
COPPER RED. MF 7/8' --> 1/2'
7/8' --> 5/8'
COPPER RED. MF 7/8' --> 5/8'
7/8' --> 3/4'
COPPER RED. MF 7/8' --> 3/4'
7/8' --> 1'
COPPER RED. MF 7/8' --> 1'
7/8' --> 1 1/8'
COPPER RED. MF 7/8' --> 1 1/8'
1' --> 1 1/8'
COPPER RED. MF 1' --> 1 1/8'
1' --> 7/8'
COPPER RED. MF 1' --> 7/8'
1' --> 3/4'
COPPER RED. MF 1' --> 3/4'
1 3/8' --> 1 1/8'
COPPER RED. MF 1 3/8'-->1 1/8'
NOTE: The MULTIDENSITY system allows for a maximum of two parallel cooling
circuits:
To connect the Tee to the proper copper pipe following the table, some M  F
adapters are available to be purchased with all the needed parts to complete the
installation.
Outdoor units twinning kit
Unit: m [ft]
2.3.4

BRAZING OF PIPING

OBLIGATION
The oxide that forms inside the pipe during the brazing process is
dissolved by the HFC fluids and causes obstruction of the
refrigerant filter. During the brazing process it is advisable to
introduce nitrogen into the piping.
2.3.5

PIPING LENGTH AND REFRIGERANT CHARGE

Use refrigerant piping made of phosphorus deoxidized copper that meets local
requirements.
Piping for systems for use with other types of refrigerant than R410a may not be able to
be used.
MODEL
MODEL
REFRIGERANT
REFRIGERANT
Refrigerant circuits x Refrigerant charge (factory charged)
Refrigerant circuits x Refrigerant charge (factory charged)
HFC R410A - F Gas - CO
equivalent
HFC R410A – F Gas – CO
equivalent
2
2
UM_MULTIDENSITY_00_Z_09_20_ML
C7540344
C7540346
C7540347
C7540349
C7540352
C7540351
C7540348
C7540350
C7540343
C7540345
C7540344
C7540354.
Example of connection
between two outdoor units
and more indoor units
connected to two parallel
cooling circuits
First branch (branch joint)
050
R410A
n x kg
1 x 11.8
t
24.3
2.3.6
ADDITIONAL REFRIGERANT CHARGE FOR STANDARD DIAMENTER
PIPING BASED ON LENGTH
The amount of refrigerant shown below is the maximum amount to be added on site.
Configuration
Configuration
Single outdoor unit system
Single outdoor unit system
Two outdoor unit system
Two outdoor unit system
Both refrigerant overcharge and undercharge will cause problem. Charge the system
with the proper amount of refrigerant. Record the added refrigerant amount on the label
attached to the control box panel for future servicing.
For more information about the external unit's refrigerant charge based on its cooling
capacity correction factor, check the Installation Manual for m-MOCU.
ADDITIONAL REFRIGERNT CHARGE
The amount of refrigerant to be added depends on the size and the total length of the
liquid piping. Calculate the amount of refrigerant to be charged according to the formula
below. Round up the calculation results to the nearest 0.1Kg.
When the piping length from the outdoor unit to the farthest indoor unit is 30.5m (100ft)
or shorter
Ø 3/4"
Amount of
[Ø 19.05] total
additional
=
length x 0.29
charge (kg)
(kg/m)
Outdoor unit
configuration
Single outdoor unit
system
Two outdoor unit
+
system
When the piping length from the outdoor unit to the farthest indoor unit is longer than
30.5m (100ft)
Ø 3/4" [Ø
Amount of
19.05] total
additional
=
length x 0.26
charge (kg)
(kg/m)
Outdoor unit
configuration
Single outdoor
unit system
+
Two outdoor
unit system
2.4

HYDRAULIC CONNECTION OF THE CONDENSATE DRAIN

The connection of the condensate drain must be carried out as decided during the design
stage.
SUPPLIED
The condensate drain pipe is connected to the collection tank.
The length of the piping brings the drain just outside the machine. A circular cut-out shape
must be opened on the base. (Round cut-out shapes can be found on the right and the left.
It's for the installer to decide which side to use).
The condensate drains by gravity.
BY THE INSTALLER
Set up a trap (A) in the vicinity of the machine, as shown in the figure.
Fill the trap with water.
Ensure a 2 - 3% gradient of the pipe down towards the drain.
Keep the same internal diameter for drain pipes of up to 4 - 5 metres. For greater lengths,
increase the section of the drain.
22
English
Max amount to be added
Max amount to be added
kg
kg
Ø 5/8"
[Ø 15.88] total
+
+
length x 0.2
(kg/m)
Total indoor
Amount (kg)
unit size)
6.0
25 ~ 37
+
12.0
38 ~ 44
45 ~ 54
55 ~ 71
71 ~ 75
Ø 5/8" [Ø
15.88] total
+
+
length x 0.18
(kg/m)
Total indoor
Amount (kg)
unit size
6.0
25 ~ 37
+
12.0
38 ~ 44
45 ~ 54
55 ~ 71
71 ~ 75
ORIGINAL INSTRUCTIONS
40.0
40.0
99.9
99.9
Unit: inch [mm]
Ø 1/2"
[Ø 12.7] total
length x 0.12
(kg/m)
Amount (kg)
3
3.5
4.5
5
6
Unit: inch [mm]
Ø 1/2" [Ø
12.7] total
length x 0.11
(kg/m)
Amount
(kg)
3
3.5
4.5
5
6