Instruction
ADM-Q..12T motion detector
The detector detects movement in the
room under surveillance
7
and initiates
an alarm. It responds most sensitively to
movement in the directions indicated by
arrows
7
B, D. The detector's function is
based on dual technology (microwave
and passive infrared). Antimask ensures
that manipulation close to the detector
(0.5 meters) is reliably detected. The
back tamper recognizes if the detector is
removed with force.
Prerequisites
The detector should be installed by peo-
ple with specialist knowledge and in
compliance with valid regulations.
The detector is only intended
for indoor use. Note the posi-
tioning instructions
Opening the detector
1. Check the scope of delivery
2. Slide up the screw-on cover
loosen the screw
2
B.
3. Pull the housing front
2
D off the base
2
C.
Fitting the detector
1. Fit the mounting base
C as follows:
2
- Define type of fastening
4
A, B. (also
refer to mounting bracket option)
- Break open three fixing holes.
- Break open aperture for cable
feedthrough
D.
4
- Fit mounting base at the proposed
height.
The mounting base should be
secured using two screws
4
A, B and the back tamper
with one screw
4
C.
2. Wire the power supply, alarm and
tamper connections according to the
options provided by the panel
Please note the end-of-line
usage guidelines for simplified
installation using the end-of-
line (EOL) concept (
3. Fold front
2
D back onto mounting
base
2
C and secure with screw
Slide down screw-on cover
Programming
To adjust the settings to the application,
move the switches into the corresponding
positions:
All manuals and user guides at all-guides.com
LED on / off
5
A
LED only indicates motion in
walk test mode.
LED lights up when detecting
motion.*
* factory setting
PIR sensitivity
5
Low sensitivity, for harsh envi-
ronments.
High sensitivity, for quiet envi-
ronments.*
* factory setting
Pet immunity
5
Suppresses alarm for pets up
to a weight of 30 kg.
Suppresses alarm for pets up
.
6
to a weight of 12 kg.*
* factory setting
1
.
A and
2
Panel
to suppress pet detection
For EN 50131-2-4 grade 3
surveillance, move the panel
back to its original posi-
tion
5
F.
Microwave sensitivity
High sensitivity, for quiet envi-
ronments.*
Low sensitivity, for harsh envi-
ronments.
* factory setting
Sensitivity setting
Turn potentiometers
5
C into the position re-
-
+
*
quired to adjust detector to
room size and field of vi-
sion.
B: Passive infrared signal
5
C: Microwave signal
8
.
5
* factory setting is the middle position
(12-meter field of vision)
Walk test
5
E,
9
).
Move the LED jumper DIP1
move the alarm control panel to walk test
mode.
Run the walk test for alarm triggering in
2
B.
the whole detection area coverage
2
A.
the detector.
Options
White light filter AO-WL10k
The white light filter is needed for applica-
tions with extreme white light interference
(> 4000 lux).
Loosen the lens currently at the positions
shown in
tor. Insert adapter
press the lens back down.
A
Wall & ceiling mounting brackets
The mounting brackets AZ-MBG3
(ceiling
be used to swivel the detector ± 45°. Use
AZ-MBG3 with switch
installations.
A
Technical data
Detection area
coverage
wide angle
Connections
5
D must be pressed in
5
G.
Supply voltage
Max. ripple
Power consump-
tion
Current limit
5
A
Alarm output
Alarm holding time
Tamper contact
Antimask
Control input
5
B,
5
C
5
B,
Self test – Fault
Warm up period
Pet immunity
EMI rejection up to
2GHz
Operating tempera-
ture
Storage tempera-
ture
5
A to ON or
Air humidity
EN60721
Type of housing
protection
7
of
EN 60529
EN 50102
- 3 -
5
F and remove from the detec-
3
B into detector and
10
10
B and wall
10
C mounting) can
10
D for EN grade 3
12 m
7
B
Power supply (2x)
Alarm (2x)
Tamper (2x)
Antimask (2x)
9.6 ... 16 V
DC
(12 V
nominal)
DC
1 V
SS
Max. 34 mA
Max. 0.9 A
Opens during
alarm
2 ... 3 s
Opens during
alarm
Opens during
alarm after 30 sec.
Walk test
(on: +12V)
Red LED: on
Trouble relay: open
60 ± 5 s
< 12 kg
< 30 kg
> 10 V/m
-10 °C ... +50 °C
-20 °C ... +60 °C
< 85 % RH
not condensing
IP41 / IK02
en