Emissions; Ionisation Current - Riello RX 70 S/PV Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.5 EMISSIONS

The burners' emission values (according
to EN 676) prove much lower than the
limits laid down by the strictest stand-
ards.
The flame's distribution and its spread
over a large surface means that the burn-
er manages to limit the formation of ther-
mal NOx, the main causes of pollutant
emission.

IONISATION CURRENT

The minimum current necessary for the control
box operation is 5 µA. The burner gives a
much higher current, meaning that checking is
not usually required. Should you want to meas-
ure the ionization current anyway, you must
open the connector (CN1) (see wiring diagram
page 8) inserted in the red wire and insert a
microammeter.
3350
CLASS LIMIT 3 = 80 mg/kWh
mg/kWh
70
60
50
40
30
NOx
20
10
0
Modulation
minimum 7 kW
11 GB
NOx
CO
maximum 35 kW
Connectors
D7256
CO
Modulation
Probe