12
STOP
13
PHOT OP
14
PHOT CLS
15
PED
16-17
24 Vac
18-19
SCA/Lock
20-21
Aerial
22-23
RX 2ch.
J3
Radio receiver
1) Cut off power supply.
2) Manually release the gate wings, move them to about half-stroke and block them again.
3) Reset power supply.
4) Send a step-by-step control signal through "TEST" push button on the card or radio control.
5) The wings should open. If not, it is sufficient to invert the move wires of the motor (3/5 for motor M1, and 6/8 for motor
M2).
6) Adjust Times and Operating logic.
TCA
It allows to adjust the automatic closure time. Check Dip-Switch N°1 is On.
The adjustment ranges from 1s minimum to 180s maximum.
TL
It allows to adjust the maximum time of the opening and closing operation.
It should be preset to about 4s more than the actual operating time of the automatic system.
The adjustment ranges from 3 s minimum to 90 s maximum.
TRAC
It allows adjustment of the delay time with which motor 1 starts the closing operation with respect to motor 2.
The adjustment ranges from. 1s minimum to 30s maximum. In the opening phase, the delay time between the
motors is 2s.
DIP 1 TCA
DIP 2 COND
DIP 3 P.P. Mod
DIP 4 CLS
8
Input, STOP push button (N.C. contact)
Input, connection of safety devices, N.C. contact (e.g. photocells).
In the opening phase: the opening of the NC contact causes the stopping of the
gate. The latter can be reopened only after removal of the obstacles.
In the closing phase: the opening of the NC contact causes the stopping of the
gate.
Input, connection of safety devices, N.C. contact (e.g. photocells).
In the opening phase: The opening of the NC contact has no effect on operation.
In the closing phase: The opening of the NC contact during closure, caused the
stopping and immediate re-opening of the gate.
Input, pedestrian push button (N.O.) Its activation is on the Motor M1 Output for the
time preset by trimmer TL.
Output: power supply of accessories, 24Vac/200mA max.
Voltage-free contact. Uutput, configuration by means of Dip-switch 7.
DIP7 OFF: Open gate LED connection , 24 Vac/3W max.
DIP7 ON: Connection to optional Lock card to control the electric lock.
Do not connect the electric lock directly to the output.
Connection to the radio receiver card of the aerial (20-screen/21-signal).
Output, second radio channel of the receiver. N.O. voltage-free contact.
Activated only in presence of insertable, two-channel receiver (CIDRA-RE C)
Insertable connector for two-channel radio receiver (CIDRA-RE C)
Built-in radio receiver for the model CIDRA-RI C
To check wire connections:
The automatic closure is enabled or disabled.
Off: disabled automatic closure
On: enabled automatic closure
The multi-flat function is enabled or disabled.
Off: disabled multi-flat function.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse of the transmitter
have no effect in the opening phase.
The operating mode of the "P.P. (Step-by-Step) Push button" and of the transmitter are selected.
Off: Operation: OPEN > STOP > CLOSE > STOP >
On: Operation : OPEN > CLOSE > OPEN >
The rapid closure is enabled or disabled.
Off: disabled rapid closure
On: enabled rapid closure. The intervention of the photocells reduces the TCA time to 3s. This
function should be used to keep the gate open only for the time required for a vehicle to pass
through. The Dip-switch 1: "TCA" must be ON.
Trimmer functions
Dip-Switch functions