3.4 
EXTERNAL 
SENSOR
If. there. is. an. external. sensor,. the. heating.
settings.SET.can.be.taken.from.the.climatic.
curves.according.to.the.external.tempera-
ture. and,. in. any. case,. limited. to. with. the.
range. values. described. in. point. 3.3. (para-
meters.PAR.22.for.zone.1,.PAR.25.for.zone.
2.and.PAR.28.for.zone.3)..
The.climatic.curve.to.be.set.can.be.selected.
from. a. value. of. 3. and. 40. (at. step. 1)..
Increasing. the. steepness. of. the. curves. of.
fig..13.will.increase.the.output.temperature.
as.the.external.temperature.decreases.
3.5 
CARD 
FUNCTIONING
The.electronic.card.has.the.following.fun-
ctions:
–. Antifreeze.protection.of.the.heating.and.
sanitary.water.circuits.(ICE).
–. Ignition.and.flame.detection.system.
–. Control.panel.setting.for.the.power.and.
the.gas.for.boiler.functioning.
–. Anti-block.for.the.pump.which.is.fed.for.
a.few.seconds.after.24.hours.of.inactivi-
ty.
–. Antifreeze.protection.for.boilers.with.an.
accumulation.boiling.unit.
–. Chimney. sweep. function. which. can. be.
activated.from.the.control.panel.
–. Temperature. which. can. be. shifted. with.
the.external.sensor.connected..
. It.can.be.set.from.the.control.panel.and.
is.active.on.the.heating.systems.of.both.
circuit.1,.circuit.2.and.circuit.3.
–. Management. of. 3. independent. heating.
circuit.systems.
–. Automatic. regulation. of. the. ignition.
power.and.maximum.heating...
. Adjustments. are. managed. automatical-
ly. by. the. electronic. card. to. guarantee.
maximum.flexibility.in.use.of.the.system.
–. Interface. with. the. following. electronic.
systems:. remote. control. SIME.HOME,.
thermal. regulator. RVS,. connected. to.
a. management. card. of. a. mixed. zone.
ZONA.MIX,. card. solar. SOLARE. and.
MODBUS. 
  NOTE: If using RVS 43 set parameter 10 
to 3 (PAR 10 = 3). 
3.6 
TEMPERATURE 
DETECTION 
SENSOR
Table 4 shows.the.resistance.values.of.the.
heating,. DHW. and. exhaust. fumes. thermi-
stors..
If  the  C.H.  flow  sensor  (SM),  C.H.  return   
sensor (SR) and the exhaust fumes sensor 
(SF)  is  faulty  or  open  circuit,  the  boiler 
will not function on either heating or DHW. 
3.7 
ELECTRONIC 
IGNITION
100
ATTENTION: curves are calculated at an ambient temperatu-
re of 20°C. The user can act on the boiler controls to change 
the environment set  for which the bend has been calculated 
by ±5°C. 
Ignition. and. flame. detection. is. controlled.
by. a. single. electrode. on. the. burner. which.
TABLE 4 (SM - SR - SF sensors)
. Temperature.(°C).
Resistance.(Ω)
.
20.
12.090
.
30.
8.313
.
40.
5.828
.
50.
4.161
.
60.
3.021
.
70.
2.229
.
80.
1.669
guarantees. reaction. in. the. case. of. acci-
dental.extinction.or.lack.of.gas.within.one.
second.
3.7.1 
Functioning 
cycle
Burner. ignition. occurs. within. max.. 10.
seconds.after.the.opening.of.the.gas.valve..
Ignition. failure. with. consequent. activation.
of.block.can.be.due.to:
–.
Lack of gas
  The. ignition. electrode. persists. in.
discharging. for. max.. 10. seconds.. If. the.
burner. does. not. ignite,. the. anomaly. is.
signalled.
. This.can.happen.the.first.time.the.boiler.
is. switched. on. after. a. long. period. of.
inactivity.due.to.the.presence.of.air.in.the.
gas.pipes.
..
It.can.be.caused.by.a.closed.gas.tap.or.by.
a.broken.valve.coil.(the.interruption.does.
not.allow.for.opening)..
–. The electrode does not discharge
. In.the.boiler,.only.the.opening.of.the.gas.
to.the.burner.can.be.detected..
. After.10.seconds.the.anomaly.is.signal-
led.. It. can. be. caused. by. an. interruption.
in.the.electrode.wire.or.if.it.is.incorrectly.
anchored. to. the. connection. points.. Or.
the.electrode.may.be.earthed.or.strongly.
worn:.it.must.be.replaced..
. Or.the.electronic.card.may.be.defective.
–. No flame detected
.
After.start-up.the.electrode.continues.to.
discharge.even.when.the.burner.is.on..
. After. 10. seconds,. the. discharge. stops,.
the.burner.is.switched.off.and.a.fault.is.
generated.
. This. fault. is. sometimes. caused. by. the.
shorting.of.the.electrode.cable.or.by.its.
improper.fixing.to.the.connection.points..
. The.electrode.is.connected.to.the.earth.
or.badly.worn.and.must.be.replaced..The.
electronic.board.is.faulty.
In.the.case.of.a.sudden.lack.of.voltage,.the.
burner.will.immediately.switch.off..
When.voltage.returns,.the.boiler.will.auto-
Fig..13