POINT C
- ASSEMBLY
Apply the safety strips in the conveyance or crushing area, depending on gate/door
height (max. 2,5 m) and apply one RED nearby each of them.
Connect each safety strip contact to the EDGE terminal of its RED.
Both NO or NC contacts may be used, hence select it trough the JP1 jumper.
Connect the safety strip to RED terminal EDGE.
It's strictly necessary to connect a 8.2kΩ 1/4w resistor in series (if the safety strip
contact is NC) or in parallel (if the safety strip contact is NO).
If 8,2 KΩ 1/4 W resistor is not connected, system stops and alarm starts.
MECHANICAL SAFETY STRIP connection
R = 8,2 KΩ
RESISTIVE SAFETY STRIP connection
16
R = 8,2 KΩ