Descargar Imprimir esta página

Mitsubishi PAC-SDW01RC-1 Manual De Instalación página 5

Ocultar thumbs Ver también para PAC-SDW01RC-1:

Publicidad

Idiomas disponibles

Idiomas disponibles

M- & P-Series Indoor Unit
Note: Default settings for Function Codes 1-28
are automatically determined by the HVAC
equipment. It may take up to 40 seconds to
enter setup and 30 seconds to exit setup.
Mode# Indoor Unit Compatibility
1
All
2
All
3
All
4
All
5
PEAD
7
All
SLZ/PLA
8 *D
PCA/PKA
8 *D
SEZ/SVZ/PEAD/PVA
9
PLA
PLA
10 *D
PCA
10 *D
SEZ/SVZ/PEAD/PVA
11 *D
PLA
11 *D
SLZ/PCA
11 *D
SVZ/PEAD/PVA
SLZ-KF/
12
PLA-A__EA7
13
SVZ/PVA
PLA
14
PCA/PKA
SLZ/PLA
15
SEZ/SVZ/PEAD
PCA/PKA
Notes:
*D
Duplicate code with multiple settings for different indoor unit types.
*1-1 When the power supply returns, the air conditioner will start 3 minutes or 1 minute later
(hinge on outdoor unit).
SDW01 Installation Manual
Function
Power Failure Auto Recovery
Indoor Temperature Detection
Lossnay Connectivity
Power Supply Voltage
Auto Mode
Filter Sign
Air Flow (Fan Speed)
Static Settings
Number of Air Outlets
High Performance Filter
Also Static Settings
Static Settings
Horizontal Vane Setting
Horizontal Vane Setting
Heater Control (Used with Mode 23)
3-D i-See Sensor Positioning
*12-1 *12-2
Optional Humidifier
Vane Differential Setting
in Heating Mode
(Cold Wind Prevention)
Frost Prevention Temp
Function Codes
Please refer to the indoor unit manual for unit specific
function codes and the description of their values. A
summary is shown in the following tables.
Setting #
Settings
1
Not Available (OFF)
2 *1-1
Available (ON) approximately 4 minute delay
1
Average data from all unit
2
Return air
3
Remote controller
1
Not Supported
2
IDU does not intake OA through Lossnay
3
IDU does intake OA through Lossnay
1
230 volt
2
208 volt
1
Energy saving cycle automatically enabled
2
Energy saving cycle automatically disabled
1
100 hours
2
2500 hours
3
No filter sign indicator
1
Quiet
2
Standard
3
High Ceiling
See "Static Pressure Settings" on page 12
1
4 directions or all 4
2
3 directions or just 3
3
2 directions or just 2
1
Not supported
2
Supported
See "Static Pressure Settings" on page 12
1
Downward setting (vanes angle setup 3)
2
Middle setting (vanes angle setup 1)
3
Dradt less setting (vanes angle setup 2) *11
1
No setting
2
Draft less setting (vanes angle setup 1)
3
Downward setting (vanes angle setup 2)
1
No backup heater present
2
Backup heater available
1
Position 1
2
Position 2
3
Position 3
1
Disable humidifier output (See mode #16)
2
Enable humidifier output (See mode #16)
1
75-82 °F TH5
2
82-90 °F TH5
3
90-100 °F TH5
1
(2 °C) 36 °F
2
(3 °C) 37 °F
*11
Because condensation may form, do not use this setting in a high-temperature,
high-humidity environment.
*12-1 Cassette must have 3D i-See Sensor installed to operate, refer to install manual.
*12-2 When the 3D i-See Sensor corner panel position is changed, change this mode.
5

Publicidad

loading