Installer Setup Options (ISU) –
ISU# ISU Name
164
Lockout Fan Speed
165
Lockout Setpoint
167
Lockout Vane Direction
170
Hide Indoor Temperature
171
Hide Indoor Humidity Display
180
Max Heat Setpoint
181
Min Cool Setpoint
190
Indoor Temperature Source
191
Indoor Temperature
Display Offset
Indoor Humidity
196
Display Offset
Auto Dry
197
Enable
198
Humidity Threshold
199
Dry Mode Offset
200
Overcool
Note: Default ISU Options are
highlighted in bold
SDW01 Installation Manual
ISU Options
• Disabled
• Enabled
• Disabled
• Enabled
• Disabled
• Enabled
• Disabled
• Enabled
• Disabled
• Enabled
40 to 90 °F (4.5 to 32.5 °C)
50 to 99 °F (10 to 37 °C)
• SDW01
• Indoor unit
-5 °F to 5 °F (-2.5 °C to 2.5 °C)
-10% RH to 10% RH
• Disabled
• Enabled
35% RH to 75% RH
2.0 °F to 9.0 °F (1 °C to 5 °C)
2.0 °F to 4.0 °F (1 °C to 2 °C)
Advanced Menu
Notes
If enabled, the controller will show a lock symbol for the fan menu, and
if the user attempts to modify the fan setting, they will be unable to.
If enabled, the controller will show a lock symbol next to the setpoint.
If the user attempts to modify the setpoint, they will be unable to.
If enabled, the controller will show a lock symbol for the vane menu, and
if the user attempts to modify the vane direction, they will be unable to.
If enabled, indoor temperature is not shown in the display.
If enabled, indoor humidity is not shown in the display.
The Max Heat Setpoint can be adjusted to any whole number between
40 and 90 °F, as well as half increments between 4.5 and 32.5 °C.
The maximum allowable setpoint depends on the model of the indoor
unit that the SDW is connected to. The maximum setpoint for each
model can be found in the indoor unit Operation or Service manual.
The Min Cool Setpoint can be adjusted to any whole number between 50
and 99 °F, as well as half increments between 10 and 37 °C. The minimum
allowable setpoint depends on the model of the indoor unit that the SDW
is connected to. The minimum setpoint for each model can be found in the
indoor unit Operation or Service manual.
SDW01: The SDW01 built-in thermistor (default).
Indoor unit: The indoor unit return air sensor.
The Indoor Temperature Display Offset can be adjusted to any whole
number between -5 and 5 °F, as well as half increments between -2.5
and 2.5 °C. 0 is the default.
The Indoor Humidity Display Offset can be adjusted to any whole
number between -10 and 10 RH. 0 is the default.
If enabled, the Auto Dry feature will run automatically based on the set
parameters.
The relative humidity value that will trigger the Auto Dry Feature
The room temperature offset above the cooling set point that causes
Auto Dry to switch from Dry mode to Cool mode
The room temperature offset below the cooling set point that causes
Auto Dry to switch from Dry mode to Cool mode