Control connection # 4 - Forward/Reverse.
Enabling the Forward/Reverse function.
Parameters to set:
Set DI3 to Forward run: P0265=4
Set DI4 to Reverse run: P0266=5
When the Forward/Reverse function is set, it will be active either in
Local or Remote mode. At the same time, the HMI keys
will remain always inactive (even if P0224=0 or P0227=0).
The direction of rotation is determined by the Forward run and
Reverse run inputs.
Clockwise direction for Forward run and counterclockwise for
Reverse run.
The speed reference can be provided by any source (as in the control
connection # 3).
Stop/Forward S1
Stop/Reverse S2
Figure 25: XC1 wiring for control connection # 4
and
XC1 Terminal Strip
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
DO1
22
C1
(RL1)
23
NO1
24
NC2
DO2
25
C2
(RL2)
26
NO2
27
NC3
DO3
28
C3
(RL3)
29
NO3
INSTALLATION ACCORDING TO THE
EUROPEAN DIRECTIVE OF ELECTROMAGNETIC
COMPATIBILITY
The inverters in sizes A to D with FA option (CFW11XXXXXXOFA) and
all the standard inverters in the other sizes have an internal RFI filter
for the reduction of the electromagnetic interference. These inverters,
when properly installed meet the requirements of the electromagnetic
compatibility directive "EMC Directive 2004/108/EC".
ATTENTION!
For using models with internal RFI filters in IT networks
follow the instructions on
Conformal Installation
For the conformal installation use:
1. Inverters on sizes A to D: with internal RFI filters option
CFW11XXXXXXOFA and other standard models.
2. Shielded output cables (motor cables) and connect the shield at
both ends (motor and inverter) with a low impedance connection
for high frequency.
Maximum motor cable length and conduced and radiated emission
levels according to the
tables 2
If a lower emission level and/or a longer motor cable were
necessary, then an external RFI filter must be provided at the
inverter input. For more information (RFI filter commercial reference,
motor cable length and emission levels) refer to the
3. Shielded control cables.
4. Inverter solid grounding.
Installation Guide
figures 17
to 19.
and 3.
tables 2
and 3.
CFW-11 | 15