Installation Guide
CABINET MOUNTING
Surface assembly:
Provide adequate exhaustion so that the internal cabinet temperature
remains within the allowed range for the inverter operations
conditions.
The power dissipated by the inverter at its rated condition is specified
in
table A.1
and
A.2
"Dissipated power in Watts – Surface Mounting".
The cabinet minimum air cooling flow requirements are as shown
in
table
1.
The position and diameter of the mounting holes are according to
figure
1.
A1
a2
øc2
Air flow
a2
a2
øc2
Air flow
Surface mounting
A1
B1
C1
D1
E1
a2
Model
mm
mm
mm
mm
mm
mm
(in)
(in)
(in)
(in)
(in)
(in)
Size
145
247
227
70
270
115
A
(5.71)
(9.73)
(8.94)
(2.75)
(10.63)
(4.53)
Size
190
293
227
71
316
150
B
(7.48)
(11.53)
(8.94)
(2.78)
(12.43)
(5.91)
Size
220
378
293
136
405
150
C
(8.67)
(14.88)
(11.53)
(5.36)
(15.95)
(5.91)
Size
300
504
305
135
550
200
D
(11.81)
(19.84)
(12.00)
(5.32)
(21.65)
(7.88)
Size
335
620
358
168
675
200
E
(13.19)
(24.41)
(14.09)
(6.61)
(25.57)
(7.88)
Size
430
1156
360
169
1234
150
F
(16.93)
(45.51)
(14.17)
(6.65)
(48.58)
(5.91)
Size
535
1190
426
202
1264
200
G
(21.06)
(46.85)
(16.77)
(7.95)
(49.76)
(7.87)
Tolerance for d3 and e3: +1.0 mm (+0.039 in)
General tolerance: ±1.0 mm (±0.039 in)
8 | CFW-11
C1
D1
a3
d3
Max. 3 mm
Air flow
øc3
(0.12 in)
a3
d3
øc3
Max. 3 mm
(0.12 in)
Air flow
Flange mounting
b2
c2
a3
b3
c3
d3
e3
mm
mm
mm
mm
mm
M
M
(in)
(in)
(in)
(in)
(in)
250
130
240
135
225
M5
M5
(9.85)
(5.12)
(9.45)
(5.32)
(8.86)
300
175
285
179
271
M5
M5
(11.82)
(6.89)
(11.23)
(7.05)
(10.66)
375
195
365
205
345
M6
M6
(14.77)
(7.68)
(14.38)
(8.08)
(13.59)
525
275
517
285
485
M8
M8
(20.67)
(10.83)
(20.36)
(11.23)
(19.10)
650
275
635
315
615
M8
M8
(25.59)
(10.83)
(25.00)
(12.40)
(24.21)
1200
350
1185
391
1146
M10
M10
(47.24)
(13.78)
(46.65)
(15.39)
(45.12)
1225
400
1220
495
1182
M10
M10
(48.23)
(15.75)
(48.03)
(19.49)
(46.53)
Figure 1: Mechanical installation details
D
Ventilation Clearances
A
Model
mm (in)
Size A
25 (0.98)
Size B
40 (1.57)
Size C
110 (4.33)
Size D
0142 T2
100 (3.94)
0180 T2
150 (5,91)
0211 T2
Size E
0105 T4
100 (3.94)
0142 T4
0180 T4
0211 T4
150 (5.91)
Size F
Size G
Tolerance: ±1.0 mm (±0.039 in)
Figure 2: Minimum clearance for inverter ventilation
Table 1: Minimun required cabinet cooling air flow
Frame
Model
A
ALL
B
ALL
C
ALL
D
ALL
CFW11 0142 T 2
CFW11 0180 T 2
CFW11 0211 T 2
E
CFW11 0105 T 4
CFW11 0142 T 4
CFW11 0180 T 4
CFW11 0211 T 4
CFW11 0242 T 4
CFW11 0312 T 4
F
CFW11 0370 T 4
CFW11 0477 T 4
CFW11 0515 T 4
G
CFW11 0601 T 4
CFW11 0720 T 4
C
D
B
C
D
mm (in)
mm (in)
mm (in)
25 (0.98)
45 (1.77)
10 (0.39)
30 (1.18)
130 (5.12)
130 (5.12)
40 (1.57)
250 (9.84)
80 (3.15)
130 (5.12)
40 (1.57)
20 (0.78)
250 (9.84)
80 (3.15)
CFM
I/s
m³/min
18
8
0.5
42
20
1.2
96
45
2.7
132
62
3.7
138
65
3.9
265
125
7.5
138
65
3.9
180
95
5.1
265
125
7.5
250
118
7.1
320
151
9.1
380
180
10.1
460
217
13
680
321
19.3