5. Commissioning, operation
Requirements for electrical connection
Cable diameter matches the cable bushing of the mating connector.
■
Cable gland and seals of the mating connector are correctly seated.
■
With cable outlets, no humidity can ingress at the cable end.
■
The IP ingress protection only applies when plugged in using mating connectors that have the appropriate IP
■
ingress protection.
Requirement for shielding and grounding
The instrument must be grounded via the process connection.
■
Use the instrument with shielded cable, and ground the shield on at least one end of the lead.
■
Pin assignment (per CiA-DR 303-1)
Circular connector M12 x 1 (5-pin)
WIKA operating instructions, pressure sensor, models D-20-9, D-21-9
Shield
UB+
UB-
CAN-High
CAN-Low
1
2
3
4
5
EN
11