Descargar Imprimir esta página

Toshiba MMC-AP0158HP Serie Manual De Instalación página 13

Publicidad

Idiomas disponibles

Idiomas disponibles

◆ Attaching the hanging bracket
fi rst
1
Remove the screws fastening hanging
onto the indoor unit.
Screw
Hanging bracket
2
Loosen the bolts fastening hanging bracket
onto the indoor unit and remove the hanging
bracket.
Bolts for fastening the hanging
bracket (Loosen these bolts.)
3
Adjust the length of the two bolts for fastening
the hanging bracket, as shown below.
7 to 12 mm
Indoor Unit
Adjust the length of the bolts for
fastening the hanging bracket.
4
Fasten the hanging bracket with the hanging
bolts and ensure that the bracket is level from
front to back and from side to side.
Hanging bolt
(locally procured)
Hanging bracket fi xing board
Washer
N
Ceiling surface
(Accessory)
(inside dimension)
Double nut
(locally procured)
Front
Model MMC-
N
AP015, AP018
867 to 872
AP024, AP027
1184 to 1189
AP036 to AP056
1501 to 1506
23-EN
5
Attach the indoor unit onto the hanging
bracket and fasten it tight with the bolts and
screws.
bracket
Bolts for fastening the hanging bracket
(Fasten the bolts tight.)
CAUTION
• The ceiling is not always level. Use the level gauge
to measure the level of the ceiling in the width and
depth directions. Adjust the bolts for the hanging
brackets so that the level error will be within 5 mm.
• Do not lower the air discharge side and the side
opposite to the selected drain pipe withdraw.
(Unit : mm)
5
Drain piping
CAUTION
Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a
heat insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.
• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation
will cause condensation to form.
• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down
(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.
• Restrict the length of the traversing drain pipe to 20 meters or less. For a long pipe, provide support brackets at
intervals of 1.5 to 2 meters to prevent fl apping.
• Install the collective piping as shown in the following fi gure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.
• A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit. Be absolutely sure to
use the fl exible hose provided for the connections with the drain pipe connecting port.
• Adhesive agents cannot be used for the drain pipe connecting port (hard socket) of the indoor unit. Be absolutely
sure to secure the pipe using the hose bands provided. Use of an adhesive agent may damage the drain pipe
connecting port or cause water to leak.
Use bolts to fasten the
hanging bracket.
Heat
insulator
Drain pipe
connecting port
(hard socket)
Adhesive
agent
prohibited
Pipe material, size and insulator
The following materials for piping work and insulating process are procured locally.
Pipe material
Insulator
– 12 –
1.5 m to 2 m
As long as possible
Support
(Approx. 10 cm)
bracket
(Collective
piping)
Downward slope
1/100 or more
Downward slope
1/100 or more
Attached drain hose
Attached
hose band
Attached hose band
Soft
Soft
VP 20 Polyvinyl
socket
socket
chloride pipe
(locally procured)
Hard vinyl chloride pipe VP20 (Nominal outer diameter Ø26 mm)
Foamed polyethylene foam, thickness: 10 mm or more
Arched shape
Trap
VP30
Incorrect
24-EN

Publicidad

loading