4. Inspection Upon Receipt of Goods
4.1 General
Special precautions and care have been taken to ensure the system arrives safe and undamaged. However, upon receipt, you should inspect
the entire shipment, including the crate and any boxes, for evidence of damage that may have occurred during transit.
4.2 Visible Damage
It is the responsibility of the person receiving the shipment to inventory and fully inspect all materials against the bill of lading or waybill
IMMEDIATELY, while the carrier representative is still present. Ensure that all items are accounted for, including number of skids and quantity
of boxes. Also, note any visible external damage that may have occurred during transit. Make all applicable notations on the delivery receipt
before signing and file a damage report with the carrier.
4.3 Concealed Damage
Within 3 to 30 days of receipt (depending on courier), unpack the system and check for any concealed damage. Check the materials
received against the detailed packing list to verify the quantity and the condition as complete and satisfactory.
Note any damage to the internal packaging. Then, request an inspection by the carrier and file a concealed damage claim. If there is a
material shortage, visit www.tripplite.com/support to file a claim.
Please contact your shipping company for all shipping damage. Tripp Lite is not responsible for any shipping damage.
4.4 Return of Damaged Goods
Should equipment be damaged and require return to Tripp Lite for repair, a representative will provide instructions and an RMA number to
expedite the return.
An RMA number must be obtained before returning equipment to Tripp Lite.
5. System Overview
The Tripp Lite SU10KMBPKX or SU20KMBPKX Maintenance Bypass Panel (MBP) is used in conjunction with an Uninterruptible Power Supply
(UPS) to maintain total continuity of power to connected load circuits when bypass of the UPS equipment is required for performance of
regular service and maintenance.
The SU10KMBPKX and SU20KMBPKX Series MBPs are available with current capacities ranging from 15 to 225 amperes with multiple input
voltage options available.
The MBP contains two or three Cutler Hammer Series C circuit breakers that are protected by a Kirk Key interlock system.
6. System Specifications
Always refer to the Ratings Label on the equipment for configuration-specific ratings. Equipment specifications and ratings in this
document represent typical equipment and may vary from the equipment provided.
6.1 Electrical
Voltage: 400Y/230VAC, 3-Phase, 4-Wire, plus ground
Frequency: 60 Hz
Current: Models available from 40A to 70A
Short Circuit Rating: up to 10kAIC
Neutral Bus Current Rating: 450A
6.2 Environmental
Operating Temperature: 32°F to 104°F (0°C to 40°C)
Relative Humidity: 5% to 95% non-condensing
Altitude: 0 to 7400 ft. (0 to 2255 m) above sea level
3