Descargar Imprimir esta página

Victron energy 24/2000 Manual página 17

Ocultar thumbs Ver también para 24/2000:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.4.5 Parallel Connection
The MultiPlus can be connected in parallel with several identical devices. To this
end, a connection is established between the devices by means of standard
RJ45 UTP cables. The system (one or more Multis plus optional control panel)
will require subsequent configuration (see Section 5).
In the event of connecting MultiPlus units in parallel, the following requirements
must be met:
A maximum of six units connected in parallel.
Only identical devices may be connected in parallel.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the
connection between the batteries and the DC distribution point must at least equal the
sum of the required cross-sections of the connections between the distribution point
and the MultiPlus units.
Place the MultiPlus units close to each other, but allow at least 10 cm for ventilation
purposes under, above and beside the units.
UTP cables must be connected directly from one unit to the other (and to the remote
panel). Connection/splitter boxes are not permitted.
A battery-temperature sensor need only be connected to one unit in the system. If the
temperature of several batteries is to be measured, you can also connect the sensors
of other MultiPlus units in the system (with a maximum of one sensor per MultiPlus).
Temperature compensation during battery charging responds to the sensor indicating
the highest temperature.
Voltage sensing must be connected to the master (see Section 5.5.1.4).
If more than three units are connected in parallel in one system, a dongle is required
(see Section 5).
Only one remote control means (panel or switch) can be connected to the system.
4.4.6 Three-phase operation
The MultiPlus can also be used in 3-phase configuration. To this end, a connection
between the devices is made by means of standard RJ45 UTP cables (the same as
for parallel operation). The system (Multis plus an optional control panel) will require
subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.6.
13

Publicidad

loading

Este manual también es adecuado para:

12/2000