Idiomas disponibles

5 – Cabinet Installation
1
5-3 Placement
Use the casters to move the UPS system for a short distance over
1
2
a level, smooth, stable surface. Do not attempt to use the casters
to move the UPS system over longer distances. The UPS system
should be moved close to its final installation location inside
its shipping container before it is unpacked from the shipping
container. Use a mechanical device of sufficient capacity to move
3
the shipping container. Warning: The UPS system could tip if it
is moved over an unstable surface. Be extremely careful when
moving the UPS system. Push the UPS system from the front or
rear, not from the sides.
4
Position the UPS system in a structurally sound area with a
2
level floor that is able to bear the weight of the UPS system,
any external battery cabinets and other equipment that will
be installed nearby. The installation site should also have a
dedicated AC circuit available that is compatible with the UPS
5
system's input requirements. (See
for more information about input requirements and floor loading
requirements.) The UPS system must be installed in a clean,
secure environment with a relative humidity less than 90% (non-
condensing). Operate the UPS system at indoor temperatures
6
between 17° C and 29° C (62° F and 84° F). Prevent damage to
cabling by using suitable protective conduits. In order to maintain
proper airflow and service access, you must maintain the following
clearances:
7
At least 100 cm clearance in front of the UPS system.
At least 50 cm clearance behind the UPS system.
At least 50 cm clearance above the UPS system.
Warning: The cooling fans circulate air from front to back. Do not
8
use any air conditioning or fan that blows air directly toward the
rear of the UPS system.
After moving the UPS system to its final location, lock the casters
3
and use the levelers
A
B
9
four levelers make firm contact with the floor.
10
For emergency use, install a fire extinguisher rated for energized
4
11
electrical equipment fires (Class C rating or exact equivalent, with
a non-conductive extinguishing agent) near the UPS system.
12
13
200803004 93-2793 SU80k manual 4C.indd E10
200803004 93-2793 SU80k manual 4C.indd E10
(continued)
Section 11 – Specifications
to stabilize the cabinet. Ensure that all
1
50 cm
100 cm
2
A
B
3
4
10
50 cm
6/16/2008 1:43:10 PM
6/16/2008 1:43:10 PM