3.2. OPERATION:
3.2.3.
MΩ Ω Ω Ω measurement at 250V
The measurement is made at a voltage of 250V
circuit current ≤ 5mA
There is a change of reading coefficient for rising values: 50MΩ (changes to X10
reading), and a change of reading coefficient for falling values: 11MΩ (changes to
X1 reading).
MΩ Ω Ω Ω measurement at 500V
The measurement is made at a voltage of 500V
circuit current ≤ 5mA
There is a change of reading coefficient for rising values: 50MΩ (changes to X10
reading), and a change of reading coefficient for falling values: 11MΩ (changes to
X1 reading).
MΩ Ω Ω Ω measurement at 1000V
The measurement is made at a voltage of 1000V
Short-circuit current ≤ 5mA
There is a change of reading coefficient for rising values: 500MΩ (changes to X10
reading), and a change of reading coefficient for falling values: 110MΩ (changes
to X1 reading).
18
MΩ Ω Ω Ω measurement:
.
DC
.
DC
.
DC
:
DC
above 1MΩ measured.
DC
:
DC
above 1MΩ measured.
DC
:
DC
above 10MΩ measured.
DC
Short-
Short-
C.A 6503