5
1
4
Fig. 7 - VC Actuator with 1 meter leadwiree cable for SPDT Controller
Attuatore VC con cavo da 1 metro per Regolatore con contatto SPDT
Actuador VC con cable de conexión de 1 m para controlador SPDT
Brown / Marrone / Marrón
Close / Chiude / Se cierra
NC
Controller
SPDT
NO
Open / Apre / Se abre
Black / Nero / Negro
L
N
Blue / Blu / Azul
Fig. 9 - VC Actuator for SPDT Controller
Attuatore VC per Regolatore con contatto SPDT
Actuador VC para controlador SPDT
CHECKOUT
1.
Raise the set point of the zone thermostat above room temperature to
initiate a call for heat. White valve position lever should move
2.
For auxiliary switch models, observe all control devices. The valve should
open and the auxiliary switch (if present) should close and make at the end
of the opening stroke to activate auxiliary equipment.
3.
Lower the set point of the zone thermostat below room temperature.
4.
Observe the control devices. The valve should close and all auxiliary
equipment should stop.
SERVICE
This valve should be serviced by a trained, experienced service
technician.
COLLAUDO E MANUTENZIONE
COLLAUDO
1. Aumentare la temperatura sul termostato di zona al di sopra di quella
misurata in ambiente. La leva bianca di apertura manuale si dovrebbe
muovere.
2. Per le versioni con micro ausiliario, osservare cosa accade ai dispositivi
collegati. La valvola dovrebbe aprirsi ed il micro ausiliario (se previsto),
raggiunta la posizione di completa apertura, dovrebbe commutare da Aperto
a Chiuso, attivando il dispositivo ausiliario collegato (ad es. una pompa).
3. Abbassare la temperatura sul termostato di zona al di sotto di quella
misurata in ambiente.
4. Osservare il dispositivo elettrico collegato. La valvola dovrebbe chiudersi ed
il dispositivo elettrico arrestarsi.
MANUTENZIONE
Per la manutenzione di queste valvole rivolgersi sempre ad un tecnico
esperto e ben addestrato.
3
6
L
M
2
N
PORT 'A'
3
SW1
SW2
6
Cam
2
CHECKOUT AND SERVICE
5
1
4
Fig. 8 - VC Actuator with Molex™ connector for SPDT Controller
Attuatore VC con connettore Molex™ per Regolatore con contatto SPDT
Actuador VC con conector Molex™ para controlador SPDT
Brown / Marrone / Marrón
Close / Chiude / Se cierra
Controller
SPST
Open / Apre / Se abre
Black / Nero / Negro
L
N
Blue / Blu / Azul
Fig. 10 – VC Actuator for SPST Controller
Attuatore VC per Regolatore con contatto SPST
Actuador VC para controlador SPST
1.
If the valve is leaking, drain system OR isolate valve from the system. Do
not remove body from plumbing.
2.
Check to see if the cartridge needs to be replaced.
3.
If the motor or other internal parts of the actuator is damaged, replace the
entire actuator assembly.
NOTE:
Honeywell hydronic valves are designed and tested for silent operation in
properly designed and installed systems. However, water noises may occur as a
result of excessive water velocity. Piping noises may occur in high temperature
(100°C) systems with insufficient water pressure.
1. In caso di filaggio della valvola occorre svuotare l'impianto o in alternativa
isolare la valvola con delle valvole manuali. Non smontare il corpo valvola
dalla tubazione.
2. Controllare che la cartuccia guida dell'otturatore non necessiti la
sostituzione. In alternativa, sostituire il corpo valvola.
3. Se il motore o alcune sue parti sono difettose, sostituire l'intero attuatore.
NOTA:
La valvole Honeywell per acqua sono progettate e collaudate per funzionamento
silensioso in sistemi progettati ed installati a regola d'arte. Tuttavia il rumore
dovuto all'acqua può verificarsi, ma solo in caso di eccessiva velocità di
circolazione. Mentre il rumore dovuto alla dilatazione delle tubazioni può
verificarsi solo a temperature elevate dell'acqua (oltre 100°) e con scarsa
pressurizzazione, non raggiungibili nei sistemi ad uso domestico.
6
3
6
L
M
2
N
6
5
4
3
2
1
PORT 'A'
3
SW1
NC
SW3
NO
SW2
6
Cam
RLY1
2

Publicidad