Installation and Connection
Table 3.1: Configuration of the switches to select the type of analog input and output signal on the CFW500-IOS
Input/
Signal
Output
Voltage
AI1
Current
Voltage
AO1
Current
NOTE!
Configuration to connect the RS485:
S1.3 = ON and S1.4 = ON: terminal RS485 ON.
S1.3 = OFF and S1.4 = OFF: terminal RS485 OFF.
Any other combination of the switches is not allowed.
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the plug-in module connector with shielded cables separated from the other wiring
(power, command in 110 V / 220 Vac, etc.), according to
on page
21. If those cables must cross other cables, it must be done perpendicularly,
keeping the minimum separation distance of 5 cm (1.97 in) at the crossing point.
Connect the shield according to the figure below:
4. Relays, contactors, solenoids or coils of electromechanical brakes installed close to the
inverters may occasionally generate interference in the control circuitry. To eliminate this
effect, RC suppressors (with AC power supply) or freewheel diodes (with DC power supply)
must be connected in parallel to the coils of these devices.
5. When using the external HMIR (refer to
that connects to the inverter must be separated from the other cables in the installation,
keeping a minimum distance of 10 cm (3.94 in).
6. When using analog reference (AI1) and the frequency oscillates (problem of electromagnetic
interference), interconnect the GND of the connector of the plug-in module to the inverter
grounding connection.
20 | MW500
Setting of
Signal
Switch S1
Range
S1.1 = OFF
0...10 V
0...20 mA
S1.1 = ON
4...20 mA
S1.2 = ON
0...10 V
0...20 mA
S1.2 = OFF
4...20 mA
Inverter
side
Figure 3.5: Connection of the shield
Section 7.2 ACCESSORIES on page
Parameter Setting
P0233 = 0 (direct reference) or 2 (inverse reference)
P0233 = 0 (direct reference) or 2 (inverse reference)
P0233 = 1 (direct reference) or 3 (inverse reference)
P0253 = 0 (direct reference) or 3 (inverse reference)
P0253 = 1 (direct reference) or 4 (inverse reference)
P0253 = 2 (direct reference) or 5 (inverse reference)
Item 3.2.7 Cable Separation Distance
Insulate with tape
Do not ground
42), the cable