8 TECHNICAL SPECIFICATIONS
8.1 POWER DATA
Power Supply:
Tolerance: - 15 % to + 10 %.
Frequency: 50/60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤ 3 % of the rated phase-to-phase input voltage.
Overvoltage according to Category III (EN 61010/UL 508C).
Transient voltage according to Category III.
Maximum of 10 connections per hour (1 every 6 minutes).
Typical efficiency: ≥ 97 %.
For further information about the technical specifications, refer to
SPECIFICATIONS on page
203.
Technical Specifications
APPENDIX B - TECHNICAL
MW500 | 45