3.3
1.1
SNOW CONDITION
To manage the alarm associated with snow, the temperature (NTC 10K/3435K) and the rain sensors must be combined.
ALARM ACTIVATED when
The measured temperature is below 2 °C and
rain has been detected.
Warning: if the temperature probe contact (13-14) is open (not connected) and the alarm is triggered, the control unit tilts the slats of the pergola to 66% of the
full opening with intermittent movements.
3.4
ACTIVATION/DEACTIVATION RAIN SENSOR OR SNOW CONDITION (RAIN+TEMPERATURE)
Sensor deactivation (60 minutes)
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s.
The buzzer emits 2 beeps.
4
QUICK LEARNING OF LIMIT SWITCH (NECESSARY IF 7/42 CHANNEL TRANSMITTERS ARE USED)
Attention: the following procedure is necessary when using 7/42 channel transmitters (type C).
Memorized
P3
(
10s)
Press P3 button and hold it for 10
seconds.
What happens with ALARM ACTIVATED
The control unit tilts the slats to 66% of full opening. The control
unit only executes hold-to-run commands.
STOP
(10 s)
Command a
manoeuvre using
a memorized
transmitter or
by means of the
wired input.
16
LR flashes
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or rain is
no longer detected. When the control unit receives a
command for automatic movement by transmitter, it
exits the alarm status.
Sensor activation
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s. The buzzer
emits a continuous sound.
complete
complete
opening
closing
...
LM flashes
Note: this automatic cycle can be stopped with any command. If working time
is exceeded (90 s), the control unit stops and emits an intermittent sound until
any button is pressed.
Factory setting
DEACTIVATED
continuous
STOP
sound
(10 s)
complete
opening
...