Descargar Imprimir esta página

Ferroli 0RGE01XA Manual De Instalación Y Usuario página 66

Publicidad

Idiomas disponibles

Idiomas disponibles

TP3 COND
5.9 Probe and bulb positioning
The control panel is equipped with a temperature probe and three bulbs.
There are two wells "A" and "B" near the heating delivery "T1" (see fig. 15).
IT IS MANDATORY to insert in the well "A" (fig. 17) the temperature probe "4" and the safety thermostat bulb "3".
Insert in the well "B" (fig. 16), the bulb of the 1st stage thermostat (1) and that of the 2nd stage thermostat (2).
Make sure the probe and bulbs reach the end of the sheath.
Place the capillaries of the bulbs and probe as shown in fig. 18.
fig. 15 - Probe and bulb wells
Legend
1
Thermostat bulb 1st Stage
2
Thermostat bulb 2nd Stage
3
Safety Thermostat bulb
4
Temperature probe
IMPORTANT
TO INSTALL ANOTHER TYPE OF TEMPERATURE CONTROL, IT IS NECESSARY TO USE AND INSTALL (AS PREVIOUSLY DE-
SCRIBED) A SAFETY THERMOSTAT COMPLYING WITH THE CURRENT REGULATIONS, WITH INTERVENTION TEMPERATURE
(SWITCHING POINT) = 110-6°C.
fig. 16 - Well B
fig. 18
cod. 30902850 - Rev 06 - 04-2022
fig. 17 - Well A
65
EN

Publicidad

loading

Este manual también es adecuado para:

Tp3 cond 65Tp3 cond 100Tp3 cond 150Tp3 cond 230Tp3 cond 370Tp3 cond 500 ... Mostrar todo