Descargar Imprimir esta página

toscano Vigilec ZERO V1Z Manual De Usuario página 43

Ocultar thumbs Ver también para Vigilec ZERO V1Z:

Publicidad

Idiomas disponibles

Idiomas disponibles

11. SETTING IMAX, IMIN AND RESTART TIME
Overload (Imax)
Current at which the overload protection trips (adjustable from 0.5 to 21 amperes
for V1Z models and from 0.5 to 30 amperes for V1Z-F models). The overload
tripping time is 7 seconds.
Overload setting (Imax)
Using a screwdriver, set Imin by turning all the way to the left [
turning all the way too to the right [
Wait a few seconds until the pump consumption is shown on the display, e.g. [
Set the maximum current 10%...15% above the pump consumption.
5. 0
21A
To continue with the setting, make sure that there is no
lack of water and that the external control output (ON/
OFF) is closed.
I.min
I.min
] or [
] (depending on model).
30A
I.min
I.max
I.min
I.min
I.max
I.min
I.max
I.max
restart
] and Imax
0FF
I.max
restart
restart
I.max
restart
restart
restart
].
5A
5A + 10% = 5,5 A
5. 5
39

Publicidad

loading

Este manual también es adecuado para:

Vigilec zero v1z-f