Technical Data
Type
Power supply
Nominal force
Nominal stroke *
Running time (OPEN)
Ingress protection
Lifetime
Duty cycle
Housing
Temperature range
Fire stability
Emission sound pressure level
Additional functions *
* Programmable with SCS software
Running speed and forces
Cable from
the top
CLOSED
OPEN
Declaration of Conformity
We declare under our sole responsibility that the
product described under "Technical Data" is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder
Member of the Board
24.02.2016
99.823.63 2.2/08/17
LDF 100/060
24 V DC / ±15% / 0,8 A
800 N
54 mm
≤ 45 sec.
IP 50
>20 000 double strokes
30 %, With cycle time 10 minutes
Stainless steel
-5 ... +75°C
30 min / 300°C
LpA ≤ 70 dB(A)
Closing edge protection activated, 3 stroke repeatings
I
4 mm
II
26 mm
III
Maik Schmees
Authorized signatory, Technical Director
LDF 100/060-IP 54
24 V DC / ±15% / 0,8 A
800 N
54 mm
≤ 45 sec.
IP 54
Closing edge protection
In the "CLOSE" direction the drive has an
active protection for the main closing
edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for
2,1 mm/sec.
10 seconds, then "CLOSE" again. If after
800 N
three attempts closing is not possible, the
drive remains in this position.
In addition, the drive is equipped with
passive protection. The closing speed in
1,4 mm/sec.
closing range 2 is reduced.
350 N
2,1 mm/sec.
400 N
Disposal
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
English
LDF 100/070
24 V DC / ±15% / 0,8 A
800 N
72 mm
≤ 45 sec.
IP 50
Significantly greater forces
can be exerted at the
secondary closing edges.
Danger of crushing hands
and fingers!
LDF 100/xxx-L/-R
5/12