Capacity tables
4 - 3
Heating Capacity Tables
EGSAH-D9W
EGSAX-D9W
EGSAX-D9WG
LWC [°C]
EBT [°C]
HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]
-10
7,36
-5
8,51
0
9,65
5
11,29
10
12,93
15
14,19
20
15,46
25
16,72
30
17,98
-10
6,08
-5
7,14
0
8,20
5
9,60
10
11,00
15
12,13
20
13,26
25
14,39
30
15,53
Legend
LWC: Leaving water temperature [°C]
EBT: Entering brine temperature [°C]
HC:
Heating capacity at maximum operating frequency, measured according to ·EN14511:2018·.
Power input at maximum operating frequency (including the controller and the pumps), measured according to
PI:
·EN14511:2018·.
Conditions
Heating capacity
Maximum heating capacity
25
35
1,64
7,04
1,91
1,59
8,15
2,05
1,55
9,55
2,20
1,63
10,83
2,18
1,72
12,40
2,16
1,63
13,98
2,14
1,55
15,56
2,12
1,47
17,14
2,10
1,38
18,71
2,08
1,42
5,84
1,64
1,37
6,86
1,72
1,33
7,98
1,79
1,40
9,30
1,83
1,48
10,62
1,86
1,40
12,05
1,84
1,31
13,49
1,82
1,22
14,92
1,79
1,14
16,36
1,77
45
55
6,51
2,35
5,98
2,79
7,70
2,47
7,24
2,89
8,88
2,59
8,49
2,98
10,07
2,52
9,31
2,86
11,26
2,45
10,12
2,74
12,43
2,34
10,89
2,55
13,61
2,24
11,66
2,37
14,78
2,14
12,43
2,18
15,96
2,04
13,20
2,00
5,36
1,99
4,88
2,34
6,45
2,08
5,99
2,44
7,54
2,16
7,10
2,54
8,81
2,21
8,33
2,60
10,09
2,26
9,55
2,66
11,26
2,17
10,46
2,49
12,43
2,07
11,38
2,33
13,61
1,98
12,29
2,16
14,78
1,88
13,20
2,00
Daikin Altherma ground source heat pump
60
5,06
2,75
5,87
2,72
6,68
2,70
7,70
2,72
8,72
2,75
9,52
2,58
10,31
2,41
11,11
2,25
11,90
2,08
4,41
2,50
5,54
2,60
6,68
2,70
7,70
2,72
8,72
2,75
9,52
2,58
10,31
2,41
11,11
2,25
11,90
2,08
3D123293
EGSAH-D9W / EGSAX-D9W / EGSAX-D9WG
4