Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 3.1). Press the DHW buttons (details 1 and 2 -
fig. 1) to increase or decrease the power (min. = 00 - max. = 60). Press the RESET button within 5 seconds and the
lighting power will remain that just set. Exit TEST mode (see sec. 3.1).
Service menu
The card is equipped with two Menus: one for configuration and the other for Service.
The configuration Menu is accessed by pressing the DHW buttons together for 10 seconds. 3 parameters modifiable
only from card for security reasons are available.
Remote
Card
Description of Transparent Parameters
control
NO
P01
Power selection (for Low-Nox versions only)
Air signal max. setpoint Offset (for Low-Nox versions
NO
P02
only)
NO
P03
Lighting step after flame detection
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
The card Service Menu is accessed by pressing the Reset button for 10 seconds. Press the Heating buttons to select
"tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" Information Menu, "Hi" History Menu, and "rE"
History Menu Reset. After selecting the Menu, press the Reset button to access it.
"tS"- Transparent Parameters Menu
The card has 24 transparent parameters also modifiable from Remote Control (Service Menu):
Remote
Card
control
01
P01
02
P02
03
P03
04
P04
05
P05
06
P06
07
P07
08
P08
09
P09
10
P10
11
P11
12
P12
13
P13
14
P14
15
P15
16
P16
EN
Description of Transparent Parameters
Gas type selection
Boiler type selection
Absolute min. power
Lighting power
Not used
Heating train
Heating pump Post-Circulation
Heating standby time
Max. heating power
Pump operation
Pump shutdown temp. during Post-Circ (P02=1)
Pump shutdown temp. during Post-Circ (P02=2)
Pump shutdown temp. during Post-Circ (P02=3)
Heating user max. setpoint
DHW pump Post-Circulation
DHW standby time
DHW max. power
DHW user max. setpoint (P02=1)
DHW user max. setpoint (P02=2)
DHW user max. setpoint (P02=3)
cod. 3540R880 - 01/2009 (Rev. 00)
Range
0=24kW, 1=32kW, 2=37kW
-20 - +20 Pa
0=Normal, 1=Low-Nox
Range
0=Natural gas,
1=LPG
1-3
0-100%
0-60%
Do not modify
1-20°C/min
0-20 minutes
0-10 minutes
0-100%
0=Post-Circulation
1=Continuous
0-100°C
0-100°C
0-100°C
31-85°C
2-255 seconds
2-255 seconds
0-100%
55-65°C
55-65°C
55-65°C
Default
0=24kW
0 Pa
0=Normal
Default
0=Natural gas
1=instantane-
ous combi
boiler
0%
50%
0
5°C/min
6 minutes
2 minutes
100%
0=Post-Circu-
lation
33°C
20°C
20°C
85°C
30 seconds
120 seconds
100%
55°C
65°C
65°C
75