2.1 Position of the stove / distance requirements
Distance requirements will only apply if the wood burning stove is to be placed close to flammable materials:
Distance to flammable
material (cm)
Asgård 1
Asgård 2
Asgård 3
Asgård 9
If the stove is positioned against a brick wall or other non-flammable material, there are no minimum distance
requirements. To facilitate cleaning and for the best use of the convection air, we recommend that you leave
approx. 5-10 cm to the wall.
If the wood burning stove is to be placed on a flammable material such as a wooden floor or carpet, it must
be placed on a non-flammable base. The floor plate should extend for at least 30 cm in front of the wood
burning stove and 15 cm on each side measured from the opening of the combustion chamber.
The wood burning stove must be installed on a floor with the adequate load-
bearing capacity. If the existing construction does not meet this requirement,
appropriate adaptation measures must be taken (e.g., a load-distributing plate).
2.2 Pipe connection
Please ensure that all local rules and regulations are complied with, including CE marking of the flue pipe.
Additionally, distance requirements to flammable material for the pipe must be respected.
The stove leaves the factory with the flue outlet mounted on the top. A flue pipe with an internal diameter of
150 mm should be used for all Asgård stoves.
To the sides
Behind the stove
(A)
30
30
30
30
A
C
Distance to
(B)
furniture (C)
10
10
25
100
10
B
Above the
stove
85
50
85
50
50
85
50
24