Descargar Imprimir esta página

Dometic SINEPOWER DSP 13 T Serie Instrucciones De Montaje Y De Uso página 22

Convertidor de ondas seno

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 78
Using the inverter
Switching to energy-saving mode
You can set the energy-saving mode using the S3 and S4 dip switches. In this way,
the battery you connect to the inverter is not discharged as quickly.
The inverter operates in energy-saving mode as long as the required power is below
the set level. If the required power exceeds the set level, the inverter works in normal
mode.
The values to be set on your inverter can be found in the following table:
Energy-saving mode
Saving mode activated when load < 1 W
Normal mode activated when load > 1 W
Saving mode activated when load < 1 W
Inverter shuts automatically down after operation
20 min in saving mode
Normal mode activated when load > 1 W
Saving mode activated when load < 45 W
Normal mode activated when load > 45 W
Saving mode activated when load < 45 W
Inverter shuts automatically down after operation
20 min in saving mode
Normal mode activated when load > 45 W
Setting net configuration
Using the switch (fig. 2 4) you can define in which net configuration the inverter
shall operate.
Parameter
An external downstream circuit breaker (RCD) is
necessary.
Operation with one load only or installation of an
external insulation monitor.
National standards shall apply!
20
TN grid
IT grid
SinePower
DIP switch
S3
S4
Off
Off
Off
On
On
Off
On
On
Dip switch
S5
Off
On
EN

Publicidad

loading