Connection Data - Lenze L-force 9400 82 200 A Serie Instrucciones Para El Montaje

Filtro rfi
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.3

Connection data

Mains
Terminal X301
Terminal data
E94AZxP0824
Connection with M8
ring cable lug
E94AZxP2004
Connection with M10
ring cable lug
Power supply module
Cable X302
Cable data
E94AZxP0824
with M8 ring cable
lug
E94AZxP2004
with M10 ring cable
lug
EDK94AZRP45 DE/EN/FR/ES/IT 2.0
Labelling
L1
L2
L3
PE
SSP94NF306
Max. conductor
cross-section
2
[mm
]
70
(2 x 70)
150
(2 x 120)
Labelling
L1'
L2'
L3'
SSP94NF307
Electrical installation
Connection data
Description
Connection of mains phases L1, L2, L3 and PE conductor
Tightening torque
[AWG]
[Nm]
2/0
12
250 mcm
20
Description
Filter output conductor (lead with ring cable lug, colour BK)
Output PE conductor (lead with ring cable lug, colour
GN/YE)
Conductor cross-section
2
[mm
]
10
70
4
Screw drive
[lb-in]
106
SW13
177
SW15
[AWG]
6
2/0
37

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

L-force e94azrp0824L-force e94azrp2004