Connecting
Electrical
Loads
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120Volt AC, single phase,
60 Hz electrical loads.
• DO NOT connect 240Vott loads to the 120Volt duplex
receptacles.
• DO NOT connect 3-phase loads to the generator.
• DO NOT connect 50 Hz loads to the generator.
• DO NOT OVERLOADTHE
GENERATOR.
See
"Don't Overload the Generator" on page 9.
Stopping the Engine
• Unplug all electrical loads from generator panel
receptacles.NEVER start or stop engine with electrical
devices plugged in and turned ON.
• Let engine run at no-load for several minutes to stabilize
the internal temperatures of engine and generator.
• Move rocker switch to "Off'
position.
• Move the fuel valve to the "Off'
position.
RECEPTACLES
120 Volt AC, 20 Amp,
Duplex
Receptacles
Eachpair of receptacles (Figure 8) is protected against
overload by a 20 Amp push-to-reset circuit breaker.
Use each receptacle to operate 120Volt AC, single-phase,
60 Hz electrical loads requiring up to 2400 watts (2.4 kW)
at 20Amps of current. Use cord sets that are rated for
125Volt AC loads at 20 Amps (or greater).
_
AUTION!
Although each receptacle is rated for
120Volts at 20 Amps (2400 watts or 2.4 kVV), the
generator is rated for a total of 3,250 watts.
Powering loads that exceed the wattage capacity of
the generator can damage it or cause serious
injuries.The total of loads powered through these
receptacles should not exceed 20 Amps.
/
8