Defrost
d0 Defrost frequency (Time between 2 starts)
dEF
d1 Maximum defrost duration (0=defrost deactivated)
Type of message during the defrost:
0=Displays the real temperature; 1=Displays the temperature at the start of the
d2
defrost; 2=Displays the dEF message
Maximum duration of the message
d3
(Time added at the end of the defrost process)
d4 Final defrost temperature (by probe) (If I00 ¹ 1)
Defrost on connecting the unit:
d5
d6 Delay of the defrost start on connecting the unit
Type of defrost:
d7
Count of time between defrost periods:
d8
0=Total real time 1 =Sum of compressor connected time
d9 Drip time when completing defrost (Shutdown of compressor and fans)
d30 Defrost strategy in SELFDRIVE mode
d31 Maximum time without defrosting (0=Deactivated)
Maximum time of cold room outside the temperature regulation range
d32
(0=Deactivated)
Exit to level 1
EP
Evaporator fans
F0 Shutdown temperature of fans
dEF
F1 Probe 2 differential if fans are shut down
F2 Shut down fans when the compressor shuts down
F3 Status of the fans during the defrost 0=Shut down; 1=Running
Delay of start-up after defrost (If F3=0)
F4
It will only actuate if it is higher than d9
Exit to level 1
EP
*
According to wizard.
It can only be modified using the configuration wizard (InI).
Description
0=NO First defrost according to d0;
1=YES, First defrost according to d6
0=Resistors;
1=Air/fans
2=Hot gas;
3=Reversal of cycle
Description
0=No 1=Yes
31
1652H4A11 Ed. 10
Value Min. Def. Max.
h.
0
6
96
Min.
0
*
255
0
2
2
Min.
0
5
255
ºC/ºF
-50
8.0
50
0
0
1
Min.
0
0
255
0
*
3
0
0
1
Min.
0
1
255
0
5
10
h.
0
96
999
h.
0
2
10
Value Min. Def. Max.
ºC/ºF
-50
45
50
ºC/ºF
0.1
2.0 20.0
0
0
1
0
0
1
Min.
0
2
99