e. Connect Next Gen PCS Filter to Outlet: Plug the Next Gen PCS Filter input power cord into a
properly grounded and compatible branch circuit outlet.
Please Note: Do not plug the Filter into a re-locatable power tap.
iii. If neither "System On", nor the "Wiring Fault" LED illuminates, there is either no voltage
© 2024 AMETEK Electronic Systems Protection / Soporte técnico: 1-800-645-9721 / espsurgex.com
i. If the branch circuit outlet is correctly wired and the magnitude of the line voltage is
acceptable (between 105 and 130 V RMS for 120V products, or between 190 and
250V RMS for 208-240V products), power will be connected to the outlets of the Next
Gen PCS Filter and the
now protected and installed correctly. You may now turn all connected equipment
back on.
ii. If the branch circuit outlet is incorrectly wired, the
and the LCD Event Monitor will display specific wiring fault information. If this occurs,
contact a licensed electrician to correct the outlet wiring. Refer to Section:
"Hardware/Next Gen PCS Filter" for LCD EVENT MONITOR display details.
at the receptacle or the magnitude of the line voltage is not acceptable (less than 105
V RMS or above 130 V RMS for 120V products, or less than 190 V RMS or above 250
V RMS for 208-240V products). If the magnitude of the line voltage is not acceptable,
specific information will be displayed on the LCD EVENT MONITOR. If this occurs,
contact a licensed electrician to trouble-shoot the abnormal voltage condition. Refer to
Section: "Hardware/Next Gen PCS Filter" for LCD EVENT MONITOR display details.
1. You may also need to verify that the Filter is operating properly.
To test, plug Next Gen PCS Filter into a known properly functioning outlet.
If the "System On" LED still does not illuminate in the functioning outlet,
contact ESP at 1-800-645-9721.
Green
"System On" LED will illuminate. Your equipment is
Red
User Manual
'Wiring Fault" LED will illuminate
31